APPENDIX A BLOWER PERFORMANCE DATA
BELT DRIVE - HIGH STATIC
NOTES:
High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model.
Unit factory shipped with sheave set at 2.5 turns open.
Air flow table represent dry coil with filters installed; SCFM correction factor for wet coil is 4%.
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1.0
--- --- --- --- --- --- --- --- --- --- 7120 3.26 6223 2.55
1.2
--- --- --- --- --- --- --- --- 6927 3.39 5924 2.61 --- ---
1.4
--- --- --- --- --- --- 6739 3.52 5602 2.65 --- --- --- ---
1.6
--- --- --- --- 6587 3.69 5245 2.67 --- --- --- --- --- ---
1.8
--- --- 6419 3.84 4877 2.70 --- --- --- --- --- --- --- ---
2.0 6261 4.01 --- --- --- --- --- --- --- --- --- --- --- ---
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
1.0
--- --- --- --- --- --- --- --- 9090 5.79 8297 5.06 7479 3.62
1.2
--- --- --- --- --- --- 8774 5.60 7914 4.83 6989 4.07 --- ---
1.4
--- --- --- --- 8471 5.43 7549 4.63 --- --- --- --- --- ---
1.6
--- --- 8209 6.14 7194 4.45 --- --- --- --- --- --- --- ---
1.8
7967 6.02 6883 5.01 --- --- --- --- --- --- --- --- --- ---
2.0 6594 4.87 --- --- --- --- --- --- --- --- --- --- --- ---
6
CPC240 HIGH STATIC BELT DRIVE
CPC180 HIGH STATIC BELT DRIVE
ESP, In H
2
O
TURNS OPEN
012345
ESP, In H
2
O
TURNS OPEN
0123456