Goodman Mfg GSH140361A Heat Pump User Manual


 
PRODUCT DESIGN
4
GSH14 SEER split system heat pump models are available
in 1 1/2 through 5 ton sizes. They are designed for 208/230
volt single phase applications.
Air is drawn through the outdoor coil by a propeller fan, and is
discharged vertically out the top of the unit. No additional
restriction (ductwork) shall be applied.
The suction and liquid line connections are of the sweat type
for field piping with refrigerant type copper. Non-back seating
valves are factory installed to accept the field run copper.
The total refrigerant charge for a normal installation is factory
installed in the condensing unit. This charge is for the match-
ing evaporator coil and a 15 foot refrigerant line set.
Systems should be properly sized by heat gain and loss
calculations made according to methods of the Air Condi-
tioning Contractors Association (ACCA) or equivalent. It is
the contractors responsibility to ensure the system has ad-
equate capacity to heat or cool the conditioned space.
GSH14 units use high-efficiency Copeland
®
scroll compres-
sors and there are a number of design characteristics which
are different from the scroll compared to the traditional recip-
rocating compressor.
Due to their design Scroll compressors are inherently more
tolerant of liquid refrigerant.
GSH14 model heat pumps do not use a reversing relay to
energize the reversing valve. The reversing valve is energized
in the cooling cycle through the "O" terminal on the room
thermostat.
This unit is for outdoor installation only. Refer to minimum
figure for clearances from the sides of the unit to full walls
and other objects.
NOTE: This unit cannot be completely enclosed. At least
one side must be unrestricted.
These clearances will help avoid air recirculation. If installing
two or more units at the same location, allow at least 24
inches between units. If only one side is restricted (for ex-
ample, against the outside wall of a house), the unit may be
placed as close as 8" to that one wall.
DO NOT locate the unit:
* Directly under a vent termination for a gas appliance.
* Within 3 feet of a clothes drier vent
* Where the refreezing of defrost water would create
a hazard
* Where water may rise into the unit.
OK!
OK!
AA AAA
A
CC
C
C
OK!
OK!
OK!
OK!
NOT
RECOMMENDED
AA
AA
AA
AA
AA
B B B
B
Model Dimensions - W x D x H
GSH140181A* 29 x 29 x 34¼
GSH140241A* 29 x 29 x 38¼
GSH140301A* 29 x 29 x 38¼
GSH140361A* 35½ x 35½ x 38¼
GSC140421A* 35½ x 35½ x 38¼
GSC140481A* 35½ x 35½ x 38¼
GSC140601A* 35½ x 35½ x 38¼