COOLING PERFORMANCE DATA GSH140301A*
EXPANDED PERFORMANCE DATA
COOLING OPERATION
MODEL: GSH140301A* / CA*F3636B6A* +TXV / MBR1200**-1 Design Subcooling 9 ±3 °F @ the liquid service valve, ARI 95 test conditions
Outdoor Ambient Temperature
65 75 85 95 105 115
Entering Indoor Wet Bulb Temperature
IDB*Airflow 596367715963677159636771596367715963677159636771
MBh 27.4 28.4 31.2 - 26.8 27.8 30.4 - 26.2 27.1 29.7 - 25.5 26.5 29.0 - 24.2 25.1 27.5 - 22.5 23.3 25.5 -
S/T 0.80 0.67 0.46 - 0.83 0.69 0.48 - 0.85 0.71 0.49 - 0.88 0.73 0.51 - 0.91 0.76 0.53 - 0.92 0.77 0.53 -
Delta T 17 14 11 - 17 15 11 - 17 15 11 - 17 15 11 - 17 14 11 - 16 14 10 -
1214 KW 1.84 1.87 1.93 - 1.97 2.00 2.06 - 2.08 2.12 2.18 - 2.18 2.22 2.29 - 2.26 2.31 2.38 - 2.33 2.38 2.46 -
AMPS 6.4 6.6 6.8 - 6.9 7.1 7.3 - 7.5 7.7 7.9 - 8.0 8.2 8.4 - 8.5 8.7 9.0 - 9.0 9.2 9.5 -
HI PR 137 148 156 - 154 166 175 - 175 188 199 - 199 215 227 - 224 241 255 - 248 267 282 -
LO PR 64 68 75 - 68 72 79 - 70 75 82 - 74 79 86 - 78 83 90 - 80 85 93 -
MBh 26.6 27.6 30.3 - 26.0 27.0 29.5 - 25.4 26.3 28.8 - 24.8 25.7 28.1 - 23.5 24.4 26.7 - 21.8 22.6 24.8 -
S/T 0.76 0.64 0.44 - 0.79 0.66 0.46 - 0.81 0.68 0.47 - 0.84 0.70 0.48 - 0.87 0.73 0.50 - 0.88 0.73 0.51 -
Delta T 17 15 11 - 18 15 12 - 18 15 12 - 18 15 12 - 17 15 11 - 16 14 11 -
70 1080 KW 1.82 1.86 1.91 - 1.95 1.99 2.05 - 2.06 2.10 2.17 - 2.16 2.20 2.27 - 2.24 2.29 2.36 - 2.32 2.36 2.44 -
AMPS 6.4 6.5 6.7 - 6.8 7.0 7.2 - 7.4 7.6 7.8 - 7.9 8.1 8.4 - 8.4 8.6 8.9 - 8.9 9.1 9.4 -
HI PR 136 146 154 - 152 164 173 - 173 187 197 - 197 212 224 - 222 239 252 - 245 264 279 -
LO PR 64 68 74 - 67 71 78 - 70 74 81 - 73 78 85 - 77 82 89 - 79 85 92 -
MBh 24.6 25.5 27.9 - 24.0 24.9 27.3 - 23.4 24.3 26.6 - 22.9 23.7 26.0 - 21.7 22.5 24.7 - 20.1 20.9 22.9 -
S/T 0.74 0.62 0.43 - 0.76 0.64 0.44 - 0.78 0.65 0.45 - 0.81 0.67 0.47 - 0.84 0.70 0.49 - 0.85 0.71 0.49 -
Delta T 18 15 12 - 18 15 12 - 18 15 12 - 18 16 12 - 18 15 12 - 17 14 11 -
945 KW 1.79 1.82 1.87 - 1.91 1.94 2.00 - 2.02 2.06 2.12 - 2.11 2.15 2.22 - 2.19 2.24 2.30 - 2.26 2.31 2.38 -
AMPS 6.2 6.3 6.5 - 6.7 6.8 7.0 - 7.2 7.4 7.6 - 7.7 7.9 8.1 - 8.2 8.4 8.6 - 8.6 8.8 9.1 -
HI PR 132 142 150 - 148 159 168 - 168 181 191 - 191 206 218 - 215 232 245 - 238 256 270 -
LO PR 62 66 72 - 65 69 76 - 68 72 79 - 71 76 83 - 74 79 87 - 77 82 89 -
MBh 27.9 28.7 31.1 33.4 27.3 28.1 30.4 32.6 26.6 27.4 29.6 31.8 26.0
26.7
28.9 31.0 24.7 25.4 27.5 29.5 22.8 23.5 25.5 27.3
S/T 0.910.810.620.400.940.840.640.410.970.870.660.421.00
0.89
0.68 0.44 1.00 0.93 0.70 0.45 1.00 0.94 0.71 0.46
Delta T19181510191815101918151020
18
15 10 19 18 15 10 17 17 14 9
1214 KW 1.85 1.89 1.94 2.00 1.98 2.02 2.08 2.14 2.09 2.14 2.20 2.27 2.19
2.24
2.31 2.38 2.28 2.33 2.40 2.47 2.35 2.40 2.48 2.55
AMPS6.56.66.87.17.07.17.47.67.57.78.08.38.0
8.2
8.5 8.8 8.5 8.8 9.0 9.4 9.0 9.3 9.6 9.9
HI PR 139 149 157 164 155 167 177 184 177 190 201 210 201 217 229 239 227 244 257 269 250 269 284 297
LO PR 65 69 75 80 68 73 80 85 71 76 83 88 75
80
87 92 78 83 91 97 81 86 94 100
MBh 27.1 27.9 30.2 32.4 26.5 27.2 29.5 31.6 25.8 26.6 28.8 30.9 25.2
25.9
28.1 30.1 23.9 24.6 26.7 28.6 22.2 22.8 24.7 26.5
S/T 0.870.780.590.380.900.810.610.390.920.830.620.400.95
0.85
0.64 0.41 0.99 0.88 0.67 0.43 1.00 0.89 0.67 0.43
Delta T20181510201915112019151120
19
15 11 20 19 15 11 19 17 14 10
75 1080 KW 1.84 1.87 1.93 1.98 1.97 2.00 2.06 2.12 2.08 2.12 2.18 2.25 2.18 2.22 2.29 2.36 2.26 2.31 2.38 2.45 2.33 2.38 2.46 2.53
AMPS6.46.66.87.06.97.17.37.67.57.77.98.28.0
8.2
8.4 8.7 8.5 8.7 9.0 9.3 9.0 9.2 9.5 9.8
HI PR 137 148 156 163 154 166 175 182 175 188 199 208 199
215
227 236 224 241 255 266 248 267 282 294
LO PR 64 68 75 79 68 72 79 84 70 75 82 87 74
79
86 92 78 83 90 96 80 85 93 99
MBh 25.0 25.7 27.9 29.9 24.4 25.1 27.2 29.2 23.8 24.5 26.6 28.5 23.3
23.9
25.9 27.8 22.1 22.8 24.6 26.4 20.5 21.1 22.8 24.5
S/T 0.840.750.570.360.870.780.590.380.890.800.600.390.92
0.82
0.62 0.40 0.95 0.85 0.65 0.42 0.96 0.86 0.65 0.42
Delta T20191511211916112119161121
19
16 11 21 19 15 11 19 18 14 10
945 KW 1.801.831.881.941.921.962.022.082.032.072.132.202.132.17 2.24 2.30 2.21 2.25 2.32 2.40 2.28 2.33 2.40 2.47
AMPS6.26.46.66.86.76.97.17.47.37.57.78.07.8
7.9
8.2 8.5 8.2 8.4 8.7 9.0 8.7 8.9 9.2 9.6
HI PR 133 143 151 158 149 161 170 177 170 183 193 201 193
208
220 229 218 234 247 258 240 259 273 285
LO PR 62 66 72 77 66 70 76 81 68 73 79 85 72 76 83 89 75 80 87 93 78 83 90 96
Shaded area is ACCA (TVA) conditions IDB: Entering Indoor Dry Bulb Temperature KW=Total system power AMPS=outdoor unit amps (comp.+fan)