Goodman Mfg GPC 14 SEER R-410 Package Air Conditioners with R-410A Air Conditioner User Manual


 
BLOWER PERFORMANCE DATA
9
Dry Coil Data
GPC14[24-60]H41A*
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
CFM 934 759 755 638 581 489 - -
WATTS957776738390 - -
CFM 990 837 801 744 696 652 601 -
WATTS 107 94 105 110 119 133 142 -
CFM 1061 989 947 925 876 - - -
WATTS 126 134 146 158 169 - - -
CFM 1022 929 894 829 797 748 695 643
WATTS 116 114 126 134 144 156 168 173
CFM 1103 1063 1012 962 937 - - -
WATTS 142 154 165 173 185 - - -
CFM 1285 1240 1202 1163 1124 1076 1046 1003
WATTS 205 218 231 244 257 268 280 288
CFM 1234 1111 1071 1024 933 922 - -
WATTS 144 140 152 164 179 183 - -
CFM 1287 1232 1186 1133 1099 1053 - -
WATTS 162 175 187 201 213 221 - -
CFM 1381 1325 1277 1233 1181 1144 - -
WATTS 195 203 217 233 247 258 - -
CFM 1272 1197 1145 1106 1055 998 947 906
WATTS 160 168 183 191 211 220 230 243
CFM 1357 1297 1244 1194 1147 1099 1049 1008
WATTS 188 202 213 228 245 255 267 284
CFM 1537 1478 1431 1386 1336 1293 1253 1208
WATTS 244 258 274 288 303 317 329 341
CFM 1418 1383 1349 1312 1275 1228 1178 1141
WATTS 242 258 273 282 299 308 320 338
CFM 1175 1635 1645 1515 1510 1450 1430 1400
WATTS 395 420 435 445 455 465 470 475
CFM 1845 1790 1715 1685 1590 1580 1530 1500
WATTS 490 505 520 535 550 560 570 575
CFM 1775 1635 1645 1515 1510 1450 1430 1400
WATTS 395 420 435 445 455 465 470 475
CFM 2025 1900 1840 1780 1725 1650 1620 1580
WATTS 575 595 620 630 645 655 660 670
NOTES:
1. Data shown is dry coil. Wet coil pressure drop is approx.
2. 0.1" H
2
O, for 2 row indoor coil; 0.2” H
2
O, for 3 row indoor coil; and 0.3” H
2
O, for 4 row indoor coil.
3. Data shown does not include filter pressure drop, approx. 0.08” H
2
O.
4. Reduce airflow by 2% for 208V operation.
230
GPC1460H41**
T4, T5
T1, T2, T3
GPC1448H41**
T1
T2,T3
T4, T5
GPC1442H41**
T1
T2,T3
T4, T5
GPC1436H41**
T1
T2,T3
T4, T5
GPC1430H41**
T1
T2,T3
T4, T5
GPC1424H41**
T1
T2,T3
T4, T5
Model Speed Volts
E.S.P (In. of H
2
O)
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230
230