E
SPECIFICACIONES
DEL
P
RODUCTO
6 www.goodmanmfg.com SS-GPC13H-SP
AIRFLOW DATA (CONT.)
Modelo Velocidad Voltios
Presión estática externa (pulgadas de H2O)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
GPC13
42H21**
Bajo 230
CFM 1,425 1,410 1,355 1,310 1,245 1,170 1,080 -
Watts 450 445 430 420 405 390 370 -
Mediano 230
CFM 1,620 1,595 1,545 1,485 1,425 1,345 1,250 1,160
Watts 550 540 525 510 495 475 450 425
Alto 230
CFM 1,945 1,935 1,875 1,800 1,730 1,635 1,535 1,440
Watts 765 755 735 715 695 670 640 615
GPC13
42H41**
Bajo 230
CFM 1,425 1,410 1,355 1,310 1,245 1,170 1,080 -
Watts 450 445 430 420 405 390 370 -
Mediano 230
CFM 1,620 1,595 1,545 1,485 1,425 1,345 1,250 1,160
Watts 550 540 525 510 495 475 450 425
Alto 230
CFM 1,945 1,935 1,875 1,800 1,730 1,635 1,535 1,440
Watts 765 755 735 715 695 670 640 615
GPC13
48H21**
Bajo 230
CFM 1,425 1,410 1,355 1,310 1,245 1,170 1,080 -
Watts 450 445 430 420 405 390 370 -
Mediano 230
CFM 1,720 1,660 1,585 1,520 1,460 1,365 1,270 -
Watts 560 555 540 530 520 490 470 -
Alto 230
CFM 2,110 2,060 1,980 1,895 1,795 1,705 1,590 1,500
Watts 785 780 765 745 720 705 665 625
GPC13
48H41**
Bajo 230
CFM 1,425 1,410 1,355 1,310 1,245 1,170 1,080 -
Watts 450 445 430 420 405 390 370 -
Mediano 230
CFM 1,720 1,660 1,585 1,520 1,460 1,365 1,270 -
Watts 560 555 540 530 520 490 470 -
Alto 230
CFM 2,110 2,060 1,980 1,895 1,795 1,705 1,590 1,500
Watts 785 780 765 745 720 705 665 625
GPC13
60H21**
“T” 1
Bajo
230
CFM 1,860 1,800 1,745 1,695 1,650 1,600 1,555 1,500
Watts 410 425 440 455 470 480 495 500
“T” 2
Mediano
230
CFM 1,990 1,945 1,885 1,835 1,785 1,740 1,695 1,645
Watts 510 520 530 545 555 570 585 590
“T” 3
Alto
230
CFM 2,100 2,045 1,985 1,945 1,895 1,850 1,800 1,750
Watts 595 610 620 630 645 660 670 680
GPC13
60H41**
“T” 1
Bajo
230
CFM 1,775 1,635 1,645 1,515 1,510 1,450 1,430 1,400
Watts 395 420 435 445 455 465 470 475
“T” 2
Mediano
230
CFM 1,845 1,790 1,715 1,685 1,590 1,580 1,530 1,500
Watts 490 505 520 535 550 560 570 575
“T” 3
Alto
230
CFM 2,025 1,900 1,840 1,780 1,725 1,650 1,620 1,580
Watts 575 595 620 630 645 655 660 670
Notes
• Data shown is dry coil; wet coil pressure drop is approximate.
• 0.1” H
2
O, for 2-row indoor coil; 0.2” H
2
O, for 3-row indoor coil; and 0.3” H
2
O, for 4-row indoor coil
• Data shown does not include fi lter pressure drop, approx. 0.08” H
2
O.
• ALL MODELS SHOULD RUN NO LESS THAN 350 CFM / TON, USE HIGHER SPEED TAP OR NEXT SIZE LARGER BLOWER ASM.
See Repair Parts list.
• Reduce airfl ow by 2% for 208V operation.