Friedrich SS10N10* Air Conditioner User Manual


 
65
HEAT / COOL ONLY ROOM AIR CONDITIONERS: TROUBLESHOOTING TIPS
Possible Solution
Possible Solution
esuaC elbissoPmelborP
Room temperature
uneven
(Heating cycle)
Check error codes. Replace as needed.Bad indoor ambient thermistor
Set at higher fan speed.Fan speed too low
Close doors, windows, etc.Opened door, windows, etc.
Enable ATSFATSF (room air sampling feature) disabled
Possible SolutionesuaC elbissoPmelborP
Unit will not defrost
(Heat pump
only models)
Replace thermistor.Bad outdoor coil thermistor
• On heat pumps with electric heat: no action needed
On model YS10N10: do not operate below 37°F/ 0°C
If outdoor air temp is higher than freezing, check
reversing valve, electric coil, outdoor thermistor,
refrigerant circuits, etc.
For proper operation: correct as needed
Temperature below 32°F/ 0°C
esuaC elbissoPmelborP
Does not heat
adequately
Exhaust or fresh air door open
Check if operating properly. Instruct customer on
proper use of control
Dirty launaM s'renwO ni dednemmocer sa naelCretl
Unit undersized
Check heat rise across coil. If unit operates
ef ciently, check if insulation can be added
to attic or walls. If insulation is adequate,
recommend additional unit or larger one
Outdoor coil thermistor or electronic control
board defective
Heater hi-limit control cycling on & off
Check for adequate fan air across heater. Check
for open hi-limit control.
Check alarms (error codes). Replace thermistor
or electronic control board.
Shorted or open supplementary heater Do ohmmeter check.
margaid gniriw elbacilppa kcehCgniriw tcerrocnI