8
FILTER
DIFF
ROOM
SET
REMOTE
6. Room temperature offset (+9°F to -9°F) (+4.5°C to -4.5°C)
Adjust to calibrate displayed room temperature to match actual room temperature.
Note: When not set to 0, ROOM will display
Press the
or button to select.
Press the
SW6 button
to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
7. Maximum compressor cycles allowed per hour (-, 2-6)
- = as many as needed, 2-6 = maximum cycles/hour
Press the
or button to select.
Press the
SW6 button
to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
(500 Hours)
8. Filter Check time (300-800, – – –)
Set Fan Run Time (in hours) when Check Filter is displayed or set to – – – to disable.
Press the
or button to select.
Note: To reset fi lter counter to zero and clear fi lter warning, press
the
and buttons simultaneously for 5 seconds.
Press the
SW6 button
to advance to the next screen.
FILTER
DIFF
ROOM
SET
REMOTE
9. Status Indicator Light (Lt 0 or 1)
0 = Status indicator never on
1 = Status indicator on with fi rst stage
Press the
or button to select.
Note: Red light indicates heating cycle and green light indicates cooling cycle
Slide the Mode switch to Heat or Cool to exit confi guration.