Friedrich RC 11 Air Conditioner User Manual


 
13
www.retroaire.com
The Right Fit For Comfort
*Refer to the charts on page 23 for electrical and optional
electric heat specifications.
1. Take unit out of packaging.
2. Slide unit into wall-sleeve. The supply duct on the cool
-
ing chassis should line up with the supply vent on the
room cabinet.
3. Slide unit out of wall-sleeve
IMPORTANT: The correct condenser air baffles must
be installed or performances may be impaired and/or
the warranty will be voided.
4. Baffle Installation - Remove baffles from kit bag sup-
plied with unit. Install left and right side baffles on the
condenser coil in existing holes:
6. Once confident that all seals are the correct size and in
the proper location and the correct baffles are attached
to the condenser coil and in the proper orientation, slide
unit into final position and tighten any tie down bolts or
screws as necessary.
Hydronic Only: Remove the 2-position connector as-
sembly from kit bag supplied with unit (this will have 2
yellow wires attached). Connect this 2-position connector
to the 2-position connection located on the bottom of the
control box panel.
To Connect Aquastat:
A.
Remove the black jumper wire located on the
bottom panel of the control box (this is also ter
-
minated with a 2-position connector).
B. Cut the jumper wire in the middle and splice the
aquastat to the jumper.
C. Place the connecter back into original location.
Refer to wire diagram on the unit for details.
7. Connect line cord.
8. See Final Inspection and Startup on page 20.
IMPORTANT: The RC/RH35 is equipped with a bracket
that allows the unit to be adjusted up and down in the chas-
sis of unleveled wall sleeves. Adjust leveler leg (Shown
below Figure B6) to desired height and tighten down using
bolts supplied on bracket.
RC/RH35 REPLACEMENT PTAC
INSTALLATION INSTRUCTIONS
• 1 Installation Manual
• 1 Lt. & Rt. Baffles
HYDRONIC
ONLY
• 1ea. 2-Position Connector & Pin Mate
• 14AWG Black Wire
• Screws
• 1” x 1” Open Cell Foam Tape
RC/RH35 INSTALLATION KIT
RC/RH35 PERFORMANCE DATA*
MODEL
COOLING
Btuh
EER
HEAT PUMP
Btuh
COP
FRESH AIR
CFM
9 9,500 10 8,500 2.8 40/35
12 11,900 10 11,400 2.9 40/35
15 14,700 9.2 13,800 2.8 40/35
18 16,900 9.1 N/A N/A 40/35
Figure B6
Figure A6
1” X 1” Supply Air
Duct Foam Tape
Baffles-Directed Inward
Toward Coil





Baffles must come in
contact with the out-
door louver.
• Make sure baffles are
directed inward toward
the center of coil.
Secure baffles tightly
to the condenser coil
using the screws pro
-
vided. (Figure A6)
5. Apply 1” x 1” open cell foam strips around supply air
duct to ensure that all the conditioned air is delivered
into the room. Failure to do so results in recirculation of
the conditioned air around the wall sleeve and through
the unit causing the unit to short cycle, thus raising
operating costs through improper heating and cooling
(Figure A6).