Friedrich MR12C1H Air Conditioner User Manual


 
27
6.2 Description of Each Control Operation
Function and Control
1. Temperature Parameters
Indoor preset temperature (T
preset
)
Indoor ambient temperature (T
amb.
2. Basic Functions
Once energized, in no case should the compressor be restarted within less than 3 minutes. In the situation that memory
function is available, for the first energization, if the compressor is at stop before de-energization, the compressor will be
started without a 3-minute lag; if the compressor is in operation before de-energization, the compressor will be started with
a 3-minute lag; and once started, the compressor will not be stopped within 6 minutes regardless of changes in room
temperature;
(1) Cooling Mode
Working conditions and process of cooling
When T
amb
. T
preset
, the unit will enter cooling operation, in which case the indoor fan, the outdoor fan and the compressor
will work and the indoor fan will run at preset speed.
When T
amb
. T
preset
-28 , the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will
run at preset speed.
When T
preset
-28 <T
amb
.< T
preset
+34 F
FF
F
F
, the unit will remain at its previous state.
Under this mode, the four-way valve will be de-energized and temperature can be set within a range from 61 to 86
If the compressor is shut down for some reasons, the indoor fan and the swing device will operate at original state.
Protection
Antifreeze protection
Under cooling and dry mode, 6 minutes after the compressor is started:
If T
evap
. 36 , the compressor will operate at reduced frequency.
If T
evap
. -30 is detected for durative 3 minutes, the compressor will stop, and after 30 seconds, the outdoor fan will stop;
and under cooling mode, the indoor fan and the swing motor will remain at the original state.
If T
evap
. 42 and the compressor has remained at OFF for at least 3 minutes, the compressor will resume its original
operation state.
Total current up and frequency down protection
If I
total
A, frequency rise will be allowed; if I
total
B, frequency rise will not be allowed; ifI
total
C, the compressor will
run at reduced frequency; and if I
total
D, the compressor will stop and the outdoor fan will stop with a time lag of 30s.
(2) Dry Mode
Working conditions and process of dry
If T
amb
. T
preset
, the unit will enter cooling and dry mode, in which case the compressor and the outdoor fan will
operate and the indoor fan will run at low speed.
If T
preset
-28 T
amb
. T
preset
, the compressor remains at its original operation state.
If T
amb
.< T
preset
-28 , the compressor will stop, the outdoor fan will stop with a time lag of 30s, and the indoor fan will
operate at low speed.
Start cooling
Stop cooling
Compressor
Original working state
Run
Stop
Outdoor fan
Indoor fan
T
preset
T
preset
-28
T
amb
Preset fan Speed
6 minutes
6 minutes
3 minutes
)
F
F
F
F
F
F