Friedrich 42 Air Conditioner User Manual


 
5
Cooling Cap. 42000 42000 48500 48500 58000 58000
Cooling Power (W) 4500 4500 5500 5500 6450 6450
SEER 9.8 9.8 9.8 9.8 9.9 9.9
Cooling SHR 0.72 0.72 0.69 0.69 0.72 0.72
ELECTRICAL HEAT DATA:
Heater Size (KW) 10.0 15.0 15.0 20.0 20.0 25.0
Heating Cap. (Btu/h) 34100 51150 51150 68200 68200 85250
Heating Power (W) 10000 15000 15000 20000 20000 25000
Heating Current (A) 41.6 62.4 62.4 83.2 83.4 104.2
HEAT PUMP DATA:
Heating Cap. (Btu/h) 40000 40000 47000 47000 59000 59000
Heating Power (W) 4000 4000 4800 4800 5636 5636
Heating Current (A) 19.0 19.0 22.0 22.0 25.0 25.0
COP 3.0 3.0 3.0 3.0 3.0 3.0
ELECTRICAL DATA:
Voltage (V) 230/208 230/208 230/208 230/208 230/208 230/208
LRA - Comp. (A) 104.0 104.0 129.0 129.0 169.0 169.0
Min. Ckt. Amps (A) + (33) 52 (33) 26,52 (40.5) 26,52 (40.5 ) 52,52 (49) 52, 52 (49), 26, 52, 52
Power Connection Hard Wire Hard Wire Hard Wire Hard Wire Hard Wire Hard Wire
PHYSICAL DATA:
Unit Width (in.) 38.00 38.00 38.00 38.00 45.00 45.00
Unit Depth (in.) 28.00 28.00 28.00 28.00 30.50 30.50
Unit Height (in.) 68.00 68.00 68.00 68.00 77.00 77.00
Shipping Weight (lbs.) 440 440 460 460 540 540
AIRFLOW DATA:
Indoor CFM 1400 1400 1400 1400 1800 1800
Fresh Air CFM 70 70 70 70 70 70
Indoor Motor 1/2 1/2 1/2 1/2 1/2 1/2
Indoor Motor Amps 3.0 3.0 3.0 3.0 3.1 3.1
Outdoor Motor 3/4 3/4 3/4 3/4 1/3 (2) 1/3 (2)
Outdoor Motor Amps 4.7 4.7 4.7 4.7 5.0 5.0
MODELS: V(E,H)B42K10 V(E,H)B42K15 V(E,H)B49K15 V(E,H)B49K20 V(E,H)B60K20 V(E,H)B60K25
COOLING DATA:
+
Value in ( ) is for the unit
power. Value outside of ( )
is for electric heat only. See
Page 12.
Section II – Dimensional Data
V(E,H)B18,24,30,36 Unit Dimensions (Inches)
Figure 1
CONDENSATE
DRAIN EXIT 2"
ABOVE FLOOR