. Ducted Condenser Air
For ducted outside air applications, the combined pressure losses of the intake and discharge air paths must not exceed
the external static capabilities of the system at the design airflow (See Table 3).
Outdoor Fan Performance
Table 1
Typical Ducted Outside Air Configuration
Figure 9
INTAKE
OUTDOOR
AIR
INTAKE
OUTSIDE
WALL
FLOOR
CEILING
EXHAUST
OUTDOOR
AIR EXHAUST
INTAKE
OUTSIDE
WALL
FLOOR
OUTDOOR AIR
EXHAUST
OUTDOOR
AIR INTAKE
CEILING
EXHAUST
BACK
OF
UNIT
OUTSIDE
WALL
Model 0.1 0.2 0.3 0.4 0.5
VE/HB18 1300 1180 1100 950 790
VE/HB24 1300 1180 1100 950 790
VE/HB30 1300 1200 1100 1000 810
VE/HB36 1730 1660 1600 1560 1400
VE/HB42 2100 2000 1900 1800 1700
VE/HB49 2600 2500 2400 2300 2100
VE/HB60 2990 2900 2800 2670 2450
Note:
Italic
type indicates performance outside the required operating
window of ± 10% of rated SCFM.