Figure 2 - Typical Two-Sided Fireplace
Installation
INTRODUCTION
Models (V)GL36PN/P and (V)GL36PNE/P are
decorative gas appliances that use a millivolt
gas control and piezo pilot or an electronic gas
control valve with an electronic ignition system
respectively. These systems require a 6", B-type
venting system for operation.
The 6" B-type vent is not supplied by FMI PROD-
UCTS, LLC. For installation guidelines, check
your B-vent instructions.
WARNING: This gas appli-
ancemustnotbeconnectedto
achimneyueservicingasolid
fuelburningappliance.
Models (V)GL36PN and (V)GL36PNE are smooth
face units for natural gas only. The (V)GL36PNP
and (V)GL36PNEP are smooth face units for
propane/LP gas only. To determine which type of
gas your unit is approved and tested for, check the
rating plate on the lift-out plate located inside the
rebox under the access panel.
BEFORE YOU BEGIN
Before beginning the installation of your appli-
ance, read these instructions through completely.
This appliance and its approved components are
safe when installed according to this installation
manual and are operated as recommended by
FMI PRODUCTS, LLC. Unless you use FMI
PRODUCTS, LLC approved components tested
for this appliance, YOU MAY CAUSE A FIRE
HAZARD!
The FMI PRODUCTS, LLC warranty will be voided
by and FMI PRODUCTS, LLC disclaims any respon-
sibility for the following actions :
A) Modication of the appliance or any of the
components manufactured by FMI PROD-
UCTS, LLC unless otherwise permitted by
FMI PRODUCTS, LLC.
B) Use of any component part not approved by
FMI PRODUCTS, LLC in combination with
this appliance.
C) Installation and/or operation in a manner other
than instructed in this manual.
D) The burning of anything other than the type of
gas approved for use in this gas appliance.
This appliance, when installed, must be electrically
grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical
Code, ANSI/NFPA 70..
The installation must conform with local codes or, in
the absence of local codes, with the current National
Fuel Gas Code, ANSI Z223.1/NFPA 54.
This appliance complies with ANSI Z21.50 as a
Vented Gas Appliance and is listed and tested by
the PFS Corporation.
WARNING: Installation of
thisapplianceshouldbedoneby
a qualied service person well
trained in the installation of such
appliances.Youwillalsoneeda
building permit from your local
BuildingandSafetyCommissioner
before installing this appliance;
otherwiseyourinsurancecompa-
nymaynotcoverthisappliance.
NOTICE: This appliance is not
intendedtobeusedasaprimary
source of heat.
SELECTING LOCATION
To determine the safest and most efcient location
for your appliance, you must take into consider-
ation the following guidelines:
1. The location must allow for proper clearances
(see Clearances, page 6). Note: This decora-
tive appliance is not designed for outdoor
installation.
2. The location should be in a place where drafts,
air conditioning ducts, windows or doors will
not affect replace heat output.
3. A location that avoids the cutting of joists
or roof rafters will make installation easier.
Figure 2 shows a typical three-sided replace
installation.
IMPORTANT: Side openings must be located at
least 3 feet from facing wall or combustible mate-
rial. End opening must be located at least 1 foot
from facing wall or combustible material.
Existing
Side
Wall
4" From Opening to
Perpendicular Wall
Access
Control Panel