Field Controls UV-16/24 Air Cleaner User Manual


 
page 5
WARNING: Never expose eyes or skin to UVC light from any source. Looking directly at the UVC light may cause permanent eye damage or blindness.
Never operate the UV-Aire
Air Purifying System out of the plenum. Avoid touching the glass portion of the lamp with your hands.
MAINTENANCE
WARNING: Disconnect power to the transformer before commencing inspection and cleaning.
NOTE: Wear disposable, non-absorbent protective gloves prior to inspection procedure in case of accidental
breakage of glass.
We recommend inspecting and cleaning the lamp at least every 6 months. Frequency depends upon the 1.
environment. Such as: the type of air filter, duration of use and replacement cycle.
To maintain maximum output intensity, replace the UV-Aire lamp annually. The lamp should operate 2.
continuously for maximum lamp life and light effectiveness.
Diagram A
Diagram B