Enviro EG40 BV Indoor Fireplace User Manual


 
Initial Installation
GAS LINE CONNECTION AND TESTING:
WARNING: Only persons licensed to work with gas piping may make the necessary gas connections to this
appliance.
GAS LINE CONNECTION
This stove is equipped with a certied exible pipe located on the right side of the unit terminating in a ” male
NPT tting. Consult your local authorities codes or the CAN/CGA B 149 (1 or 2) installation code in Canada, or
in the USA gas installations follow either local codes or the current edition of the National Fuel Gas Code ANSI
Z223.1.
The efciency rating of this appliance is a product thermal efciency rating determined under continuous
operating conditions and was determined independently of any installed system.
The appliance and its shutoff valves must be disconnected
from the gas supply piping system during any pressure
testing where the pressure exceeds  PSIG (3.45 KPa)
or damage will occur to the valve.
The appliance must be isolated from the gas supply
piping system by closing its individual manual shutoff
valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 
psig (3.45 KPa).
Always check for gas leaks with a soap
and water solution after completing the
required pressure test.
TO TEST VALVE PRESSURES
The pressure taps are located on the left side of the valve
Turn set screw 1 turn counter clockwise to loosen,
Place
5
/16” (8 mm) I.D. hose over pressure tap system.
Check pressures using a manometer.
When nished, release pressure, remove hose & tighten setscrew.
Natural Gas Propane
Front Burner #48 DMS #55 DMS
Rear Burner #43 DMS #54 DMS
Manifold Pressure 3.8” W.C. (0.95 KPa) 11.0” W.C. (2.7KPa)
Min. Manifold Pressure 1.1” W.C. (0.27KPa) 2.7” W.C. (0.67KPa)
Max Supply Pressure 7.0” W.C. (1.74KPa) 12.0” W.C. (2.98KPa)
Min. Supply Pressure 5.0” W.C. (1.24KPa) 11.5” W.C. (2.86KPa)
Max BTU/hr Input 38,000 BTU/hr (11.1KW) 38,000 BTU/hr (7.76KW)
Min. BTU/hr Input 20,000 BTU/hr (5.9 KW) 20,000 BTU/hr (5.9KW)
NEVER USE AN OPEN FLAME FOR LEAK TESTING.
O
L
I
T
P
TPTH TP TH
IN OUT
H
I
L
O
N
O
F
O
F
L
I
P
T
O










Figure 10: Fully Labeled Gas Valve.
Table 4: Pressure and BTU Information.
12