Enviro Cara Stove User Manual


 
27
Vent Pipe
Inside Finished Collar
Dry Wall
Wall Thimble
Exterior Wall
Siding
Minimum Vent Terminal 36”
(914mm) High Snorkel Kit.
Figure 46: Installation for Rear Vented;
33,500 Btu/hr.
Place the unit into position.
Attach a small section of pipe on the unit and mark exterior
wall where vent would pass through the wall.
Cut a 10” (25.4 cm) minimum hole in the wall to maintain
clearances to combustibles. Frame hole as shown in Figure
32.
Install a wall thimble, interior nished collar, and the vent
section through the wall.
THIS UNIT MUST BE VENTED WITH A 36” (91 cm) SNORKEL
KIT.
Seal around the vent terminal to the structure using a non-
hardening mastic.
Also refer to INITIAL INSTALLATION - VENT CONFIGURATIONS AND
RESTRICTOR SETTINGS and INITIAL INSTALLATION - HORIZONTAL
INSTALLATION.
Initial Installation
QUALIFIED INSTALLERS ONLY
CONVERTING TOP VENTED INTO REAR VENTED:
This unit has been shipped as a 33,500 Btu/hr top-vented freestanding unit. This unit can be converted
Figure 45: Converting Top Vented into Rear Vented.
INSTALLATION OF REAR VENTED APPLIANCE:
to a rear vented unit for use with a 36” (915
mm) snorkel. Also refer to INITIAL INSTALLATION
- INSTALLATION OF REAR VENTED APPLIANCE.
1. Carefully remove the trivet and the
stovetop. Place on a soft surface as not to
damage the nish.
2. Remove the four (4) ” screws that hold
the ue collar elbow to the unit body.
3. Carefully remove the elbow being sure not
to damage the gasket that is glued to the
ue collar elbow, it seals the ue to the
rebox (see Figure 42).
4. Turn the elbow 180° to the rear vent
position and re-fasten with the screws
removed in step 2.
Venting
Gasket
Rotate 180
o