Empire Comfort Systems VFP32FP Indoor Fireplace User Manual


 
Page 720101-0-0306
Water vapor is a by-product of gas combustion. An unvented room
heater produces approximately one (1) ounce (30ml) of water for
every 1,000 BTU's (.3KW's) of gas input per hour.
Unvented room heaters are recommended as supplemental heat (a
room) rather than a primary heat source (an entire house). In most
supplemental heat applications, the water vapor does not create a
problem. In most applications, the water vapor enhances the low
humidity atmosphere experienced during cold weather.
The following steps will help insure that water vapor does not
become a problem.
1. Be sure the heater is sized properly for the application, including
ample combustion air and circulation air.
2. If high humidity is experienced, a dehumidifier may be used
to help lower the water vapor content of the air.
3. Do not use an unvented room heater as the primary heat
source.
This heater shall not be installed in a confined space or unusually
tight construction unless provisions are provided for adequate
combustion and ventilation air.
The National Fuel Gas Code, ANSI Z223.1 defines a confined space
as a space whose volume is less than 50 cubic feet per 1,000 Btu per
hour (4.8m
3
per kw) of the aggregate input rating of all appliances
installed in that space and an unconfined space as a space whose
volume is not less than 50 cubic feet per 1,000 Btu per hour (4.8m
3
per kw) of the aggregate input rating of all appliances installed in
that space. Rooms communicating directly with the space in which
the appliances are installed, through openings not furnished with
doors, are considered a part of the unconfined space.
Unusually Tight Construction
The air that leaks around doors and windows may provide enough
fresh air for combustion and ventilation. However, in buildings
of unusually tight construction, you must provide additional fresh
air.
Unusually tight construction is defined as construction
where:
a. Walls and ceilings exposed to the outside atmosphere have
a continuous water vapor retarder with a rating of one perm
or less with openings gasketed or sealed, and
b. Weather-stripping has been added on openable windows
and doors, and
c. Caulking or sealants are applied to areas such as joints
around window and door frames, between sole plates and
floors, between wall-ceiling joints, between wall panels, at
penetrations for plumbing, electrical, and gas lines, and at
other openings.
If your home meets all of the three criteria above, you must
provide additional fresh air. See “Ventilation Air From
Outdoors,” page 8.
Determining if You Have a Confined or Unconfined Space
Use this worksheet to determine if you have a confined or
unconfined space.
Space: Includes the room in which you will install heater plus any
adjoining rooms with doorless passageways or ventilation grills
between the rooms.
1. Determine the volume of the space (length x width x height).
Length x Width x Height = cu. ft. (volume
of space)
Example: Space size 16 ft. (length) x 10 ft. (width) x 8 ft. (ceiling
height) = 1,280 cu. ft. (volume of space)
If additional ventilation to adjoining room is supplied with
grills or openings, add the volume of these rooms to the total
volume of the space.
2. Divide the space volume by 50 cubic feet to determine the
maximum BTU/Hr the space can support.
(volume of space) ÷ 50 cu. ft. = (maximum
BTU/Hr the space can support)
Example: 1,280 cu. ft. (volume of space) ÷ 50 cu. ft. = 25.6
or 25,600 (maximum BTU/Hr the space can
support)
3. Add the BTU/Hr of all fuel burning appliances in the space.
Vent-free heater
BTU/Hr
Gas water heater BTU/Hr
Gas furnace BTU/Hr
Vented gas heater BTU/Hr
Gas fireplace logs BTU/Hr
Other gas appliances* + BTU/Hr
Total = BTU/Hr
Example: Vented gas heater 20,000 BTU/Hr
Vent-free heater + 18,000 BTU/Hr
Total = 38,000 BTU/Hr
*Do not include direct-vent gas appliances. Direct vent draws
combustion air from the outdoors and vents to the outdoors.
4. Compare the maximum BTU/Hr the space can support with
the actual amount of BTU/Hr used.
BTU/Hr (maximum the space can support)
BTU/Hr (actual amount of BTU/Hr used)
Example:
25,600 BTU/Hr (maximum the space can support)
38,000 BTU/Hr (actual amount of BTU/Hr used)
Warning: If the area in which the heater may be operated is smaller
than that defined as an unconfined space or if the building is of
unusually tight construction, provide adequate combustion and
ventilation air by one of the methods described in the National Fuel
Gas Code, ANSI Z223.1, Section 5.3 or applicable local codes.
WATER VAPOR: A BY-PRODUCT OF UNVENTED ROOM HEATERS
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR