INSTALLER/CONFIGURATION MENU
With Heat or A/C selected, press and hold the Menu button for at least 5 seconds. The display will show item #1 in the table
below. Press Menu to advance to the next menu item. Press
or to change a menu item options.
INSTALLER/CONFIGURATION MENU
Menu
Ref.
HP SS Press
Button
Displayed
(Factory Default)
Press
or to
select from listed op-
tions
Comments
1 1 1 MENU (MS 2) HP 1, HP 2, SS 1 Selects Multi-Stage (MS 2 No Heat Pump),
Heat Pump 1 (HP 1, 1 compressor),
Heat Pump 2 (HP 2, 2 compressor or 2 speed
compressor), or Single Stage (SS 1)
2 2 2 MENU (GAS) for SS or MS ELE GAS setting: furnace controls the blower
ELE setting: thermostat controls the blower
3 3 3 MENU E (On) OFF Selects Energy Management Recovery (EMR)
On or OFF. (Not available in -non-program-
mable mode)
4 4 MENU CR Heat (ME) SL, FA Selects Adjustable Anticipation, cycle rate, Heat
(This item only appears when MS 2 or SS 1 is
selected above)
5 4 MENU CR Heat A/C
(ME)
SL, FA Selects Adjustable Compressor Anticipation
(Heat Pump) This item only appears when
HP 1, HP 2 is selected above
6 5 5 MENU CR A/C (ME)
or
CR Aux Heat (FA)
SL, FA
SL
Selects Adjustable Anticipation, cycle rate, cool
(when MS 2 or SS 1 is selected above.) or
Selects the cycle rate for Auxiliary stage (when
HP 1 or HP 2 is selected above)
7 6 6 MENU CL (OFF) CL On Compressor Lockout Time
8 7 7 MENU Heat A/C Off
or
Aux Heat A/C Off
Heat A/C Off,
Heat Off with Fan icon,
Heat Off without Fan icon
A/C Off
System Mode Confi guration
with Automatic Changeover capability
9 8 8 MENU CO (OFF) CO On Selects Compressor Optimization
10 9 9 MENU dL (On) dL OFF Selects Display Light On or OFF
11 10 10 MENU 0 HI
(current temperature)
1 HI, 2 HI, 3HI, 4 HI,
1 LO, 2 LO, 3 LO, 4 LO
Adjustable Ambient Temperature Display
12 11 11 MENU °F °C Selects Fahrenheit/Celsius Temperature Display
13 12 12 MENU P (0) 7 Defaults to P (0) non-programmable
P (7) is 7-day programming
14 13 13 MENU PS (2) 4 Selects Program periods per day:
4 = Morn, Day, Eve, Night
2 = Day, Night
15 14 MENU Heat FA (On) OFF Fast Heat option may be disabled by
selecting OFF. NA to SS or HP1 confi g.
16 15 14 MENU A/C FA (On) OFF Fast Cool option may be disabled by
selecting OFF. NA to SS or HP1 confi g.
17 16 15 MENU dS (On) Off Selects Automatic Daylight Saving Time option
18 17 16 MENU HL Heat
(99)
62 to 98 Select's Limited HEAT Range
19 18 17 MENU LL A/C
(45)
46 to 82 Select's Limited A/C Range
20 19 MENU dF (0) 1 to 9 Selects dF (dual Fuel) setting. 0 is Off
(If dual Fuel option is required, a selection of 5
is recommended)
MENU Cd
(60)
0 to 99 Selects compressor delay in seconds when dF
is greater than 0
21 20 18 MENU A/C On (o) Heat On (b) Selects operation of the reversing valve terminal
(O/B) output as an O or B terminal