DISPLAY
A Room noise level indicator (when in audio position).
B High level of contamination. Set to (3) or auto.
C Medium level of contamination. Set to (2) or auto.
D Lower level of contamination. Set to (1) or leave at this setting.
E Indicates time to clean filters according to schedule.
F Indicates filter must be changed.
G Fan speed indicator.
4
H
D
E
F
CC
C
G
I
FILTRATION STAGES
To ensure the highest quality of air, the air cleaner has a specially designed triple stage filtration
system. When air enters the unit, it passes through three filters and is then let out into the room
again.
Stage 1 Two pre-filters remove large particles such as strands of hair.
Stage 2 The electrostatic main filter (Reference No. EF100) removes smaller particles such
as pollen, mildew spores, dust.
Stage 3 Carbon filter, (Reference No. EF101). The carbon filter reduces the amount of gases
and odor (for example, tobacco smoke) from the indoor air. (The carbon filter will
reduce the air flow slightly.) The unit can be run without the carbon filter.
CAUTION:
High voltage. Turn off the power switch and unplug before servicing.
This equipment should be inspected frequently and collected dirt
removed from it regularly to prevent excessive accumulation that may
result in flashover and/or risk of fire.
FOR BEST RESULTS
Place the air cleaner on the floor next to a wall. The air cleaner draws in air at floor level and blows
it out at the top. Place the air cleaner along the same wall as the room heater so that the rising
warm air coincides with the air flow of the cleaner. When using two or more units in one room,
place them along the same wall, as far apart as possible.
CAUTION:
Do not place under a smoke detector. The cleaned air may delay the
smoke detector operation in the event of a fire.
FILTER CLEANING INTERVALS
Depending on the level of air contamination, we recommend that you follow the cleaning procedure
every two months or when the indicator on the display lights up.
The main filter may need cleaning more frequently if dust is visible on the upper filter surface.
Replace the main filter once a year or more frequently if necessary or when the indicator on the
display lights up.
When using the carbon filter, replace every three to six months or sooner if you are no longer able
to detect a reduction in odors.
A
B
C
D
E
F
G