Ducane (HVAC) (2/4)SH13 Heat Pump User Manual


 
# 48369K005 Page 11
Figure 9
Wiring Diagram
P/N 48349-001
208/230V-1-60
G
W1
CRO
BLK
RED
YEL
RED
CONTACTOR
THERMOSTAT
HIGH PRESSURE
SWITCH
(IF USED)
L1
T1
T2
L2
C
H
F
CONDENSER
FAN MOTOR
COMPRESSOR
CONTACTOR
COMPRESSOR
CONTACTOR
DUAL
CAPACITOR
COMPRESSOR
TRANSFORMER
C
S
R
WHT
L2
L1
BLK
BRN
PUR
RED
RED
BLK
208V
240V
24V
INDOOR
BLOWER
MOTOR
NOTE:
IF ANY OFTHE ORIGINAL
WIRE IS REPLACEDTHE
SAME SIZE ANDTYPE WIRE
MUST BE USED. USE
COPPER CONDUCTOR ONLY,
MIN 75°C WIRE.
LINEVOLTAGE FIELD INSTALLED.
WARNING-
ELECTRIC SHOCK HAZARD.
UNIT MUST BE GROUNDED
IN ACCORDANCE WITH
NATIONAL AND LOCAL CODES.
S4
S1
K1
T1
B3
B4
K1-2
C12
B1
K1-1
BLU
YEL
C4
CAPACITOR
H
M
L
C
SEE CHART
FOR WIRING
MOTOR
SPEED TAPS
NO
NC
C
P-3
BLOWER
CONTROL
A15
NC
C
CMC1
BLK
C
G
XFMR-R
R
XFMR-C
W1
C
L
R
O
Y1
FAN
O-OUT
LO-PS
DF
HI-PS
COMMON
Y1 OUT
2
2
CMC1
S6
L1
24V
FUSE
Y
A15
BLOWER
CONTROL
W2
RED
YEL
BLU
WHT
GRN
ORN
RED
BLU
BLU
YEL
BLU
DIAGNOSTIC DISPLAY
Note: Because the pressure switches are monitored only when "Y1" (Input) is active, the code for
pressure switch open will not be seen when "Y1" is off. Instead, the “Normal Operation" or
“Anti-Short Cycle Lockout” code will be seen.
When a pressure switch opens and causes a short cycle lockout, the pressure
switch-open code will be seen until it closes, then the short cycle lockout code
will flash unless it has already expired.
W1 & W2 CAN BE USEDTO STAGE ELECTRIC HEAT
ACCESSORY ON 15 & 20KW MODELS.
5, 7.5, & 10KW HEATER ACCESSORIES FUNCTION
OFF W1 ONLY.
BLK
BLK
DEFROST
CONTROL
BLU
WHT
REVERSING
VALVE
DEFROST
T'STAT
DEFROST CONTROL
P-1
P-2
P-4
P-6
P-5
CONNECTION MUST BE JUMPERED
WHEN PRESSURE SWITCH IS NOT USED.
2
Unit
Factory Shipped
Settings
Cooling Input (BLK)
24 LOW
30 MED
36 HIGH
42 LOW
48 MED
60 HIGH
Mode Green LED (DS2) Red LED (DS1)
No Power to Board Off Off
Normal Operation/ Power to Board Simultaneous Slow Flash
Anti-Short Cycle Lockout Alternating Slow Flash
Low Pressure Switch Fault Off Slow Flash
Low Pressure Switch Lockout Off On
High Pressure Switch Fault Slow Flash Off
High Pressure Switch Lockout On Off
L
M
HC
BLOWER SPEED CHART