Drolet 1200 Stove User Manual


 
CLEARANCES
It is of utmost importance that the clearances to combustible material be scrupulously
respected upon installation of the stove you have selected. Refer to the tables below :
Figure 8: Clearances to combustibles
Single wall pipe / Double wall pipe
CANADA
A B C D E F
SIBERIAN-1200 15/10 8/8 7/6 20.4/15.4 20/20 19.4/18.4
SIBERIAN-1600 15/12 14/12 12/8 20.8/17.8 27.2/25.2 25.5/21.5
SIBERIAN-2000 15/10 10/8 7/5 21.3/16.3 24.9/22.9 22.1/20.1
Single wall pipe / Double wall pipe
USA
A B C D E F
SIBERIAN-1200 17/12.5 8/8 10/7 22.4/17.9 20/20 22.4/19.4
SIBERIAN-1600 15/12 14/12 12/8 20.8/17.8 27.2/25.2 25.5/21.5
SIBERIAN-2000 15/10 10/8 7/5 21.3/16.3 24.9/22.9 22.1/20.1
Floor to ceiling height must be at least 7' (84") in all cases.
The clearance between the flue pipe and a wall are valid only for vertical walls and for
vertical flue pipe.
The flue pipe must not go through roof trussing, an attic, a wardrobe or similar spaces;
neither a floor or combustible partition.
A flue pipe crossing a combustible wall must have a clearance of 18" minimum.
To reduce flue pipe clearances from combustible materials, contact your local safety
department.
13