FLOOR PROTECTOR
Your wood stove should be placed on a non-combustible surface. The floor protector
should be under the stove, eighteen inches beyond the front and eight inches beyond each
side of the fuel loading and ash removal opening. If there is a horizontal section of
chimney connector, the floor protector should go under it and two inches beyond each
side.
The floor protector should exceed the stove as follows:
FRONT
18’’
(460 mm)
SIDES
8’’
(200 mm)
BACK
8’’
(200 mm)
CLEARANCES FROM COMBUSTIBLES
MINIMUM 2.13 m (7ft.) CEILING UNLESS
SHIELDED
MEASURED FROM
OUTSIDE EDGE OF
STOVE
MEASURED FROM
CONNECTOR
(a) Using single wall pipe: Side
Back
Corner
A. 16" (406 mm)
B. 12" (305 mm)
C. 8" (203 mm)
D. 25" (635 mm)
E. 18" (457 mm)
F. 19" (483 mm)
(b) Using single wall pipe with pipe shield: Side
Back
Corner
A. 14" (356 mm)
B. 5" (127 mm)
C. 8" (203 mm)
D. 23" (584 mm)
E. 11" (279 mm)
F. 19" (483 mm)
(c) Mobile Home inst. using insulated pipe: Side
Back
Corner
A. 14" (356 mm)
B. 3" (76 mm)
C. 8" (203 mm)
D. 22" (559 mm)
E. 8" (203 mm)
F. 18"(457 mm)
d) Mobile Home inst. using Double-Wall pipe: Side
Back
Corner
A. 14" (356 mm)
B. 6" (152 mm)
C. 8" (203 mm)
D. 23" (584 mm)
E. 12" (305 mm)
F. 19" (483 mm)
(e) Alcove inst. using Double-Wall pipe: Side
Back
A 11" (279 mm)
B. 7" (180 mm)
D. 20" (510 mm)
E. 13" (330 mm)
6