Operating Instructions XWA11V
1598003200
Weiss Instruments, Inc. 905 Waverly Ave. Holtsville, NY 11742 631-207-1200 www.weissinstruments.com
7
13. PARAMETER MAP
LABEL
DESCRIPTION
COOLER
VALUES
DEFAULT
**
FREEZER
VALUES
LEVEL
RANGE
ot
Thermostat probe calibration
0
0
Pr2
[-12,0°C <> 12,0°C] [-
21°F <> 21°F]
CF
Temp measurement unit
F
F
Pr2
°C - °F
rES
Resolution (only °C)
in
in
Pr2
dE - in
UT
Display update
60
60
Pr2
0 <> 255 (sec)
OnF
Off function enabling
Y
Y
Pr2
N - Y
ALU
High Temp alarm setting **
50
30
Pr1
°C[ ALL <> 150,0°]
°F[ ALL <> 302°]
ALL
Low Temp alarm setting **
25
-20
Pr1
°C[ -50.0° <> ALU]
°F[-58 <> ALU]
AFH
Temp alarm differential
2
2
Pr2
[0,1°C <>25,5°C]
[1°F <> 45°F]
ALd
Temp alarm delay
30
30
Pr1
0 <> 255 (min.)
dAo
Delay of Temp alarm at start-up
1.5
1.5
Pr2
0 <> 24.0 (Hrs / 10 min.)
EdA
Alarm delay at the end of defrost
30
30
Pr2
0 <> 255 (min.)
dot
Delay of Temp alarm after closing
the door
15
15
Pr2
0 <> 255 (min.)
LHt
Light timer
15
15
Pr1
0 <> 255 (min.)
doA
Open door alarm delay
15
15
Pr1
0 <> 255 (min.)
OA1
First relay configuration
Alr
ALr
Pr2
ALr - LHt - OnF
oA2
Second relay configuration
LHt
LHt
Pr2
ALr - LHt - OnF
AOP
Alarm relay polarity
CL
CL
Pr2
OP - CL
i1P
Digital input 1 polarity
op
oP
Pr2
OP - CL
i1L
Door switch to turn light ON
y
y
Pr2
n - Y
i1F
Digital input 1 operating mode
dor
dor
Pr2
EAL - dor- dFr - LHt
i2P
Digital input 2 polarity
CL
cL
Pr2
OP - CL
i2F
Digital input 2 operating mode
Pan
PAn
Pr2
EAL - Pan - dFr - LHt
did
Time interval/delay for digital
input alarm
0
0
Pr2
0 <> 255 (min.)
tbA
Alarm relay disabling
n
n
Pr2
n - Y
PbC
Kind of probe
ntc
ntc
Pr2
PtC - ntC
dP1
Real T° Probe 1
Pr2
(probe value)
rEL
FW release
Pr2
read only
Ptb
Parameter map
Pr2
read only