TRANSPORT
INSTALLATION
4
CAUTION!
TRANSPORT
During transport, the heat pump
must not be tilted more than 45° (in either direction).
The unit should be transported to the final
installation site on a wooden pallet. The heat pump
can be transported either by means of a lift truck or
using 3/4" pipes to be passed through the openings
provided in the base plate or in the frame.
The heat pump and transport pallet
are only connected by the packaging film.
When using 3/4" carrying pipes, be sure to secure
them against shifting so as to avoid injuries (to your
hands) during transport!
When slipping the carrying pipes through the frame,
care must be taken that no components (in particular
the plastic condensate pan or the drain pipe socket)
are damaged.
CAUTION!
INSTALLATION
5.1 General
The unit should always be installed on a
permanently level, smooth and horizontal floor. The
base frame (with its contact surfaces) should make
close contact with the floor in order to prevent any
structure-borne noise from being transmitted. If this
is not possible, additional sound-absorbing
measures might become necessary. It must be
possible to carry out servicing activities without any
problems. This is assured if a clearance of 1.2m is
maintained all around the unit.
The air intake and discharge
openings must not be restricted nor obstructed.
5.2 Condensate Line
The condensation water that may collect during
operation must be drained in a place protected from
frost. The heat pump must be positioned horizontally
so that proper discharge can be ensured. The
condensation water pipe must have a minimum
diameter of 50 mm and should be discharged to the
sewer drain in a frost-proof location.
The condensate pipe has to be placed centered
unterneath the drain pipe fitting of the condensate pan
(see also dimensioned drawing in the Appendix). Al-
ternative condensate discharge options have to be
agreed with the manufacturer.
Do not discharge the condensate directly into
septic pits or cesspools as the evaporator is likely
to be destroyed by the aggressive vapours
generated there.
5
1,2 m1,2 m
1,2 m
1,2 m
CAUTION!