Desa VF-18N-EMU Electric Heater User Manual


 
111826-05
For more information, visit www.desatech.com
8
Carefully follow the instructions below. This will ensure safe in-
stallation into a masonry, UL127-listed manufactured fireplace, or
listed vent-free firebox.
Minimum Clearances For Side Combustible
Material, Side Wall, and Ceiling
A. Clearances from the side of the fireplace cabinet to any com-
bustible material and wall should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf, etc. is made of
combustible material and protrudes 3
1
/2" from the wall. This
combustible material must be 4" from the side of the fireplace
cabinet (see Figure 4).
Note: When installing your gas logs into a manufactured fire-
box, follow firebox manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the fireplace opening to the ceiling
should not be less than 42 inches.
Figure 4 - Minimum Clearance for Combustible to Wall
*Minimum 16 inches from Side Wall
*
Example
INSTALLATION
Continued
Heat Resistant
Material
(A)
Figure 5 - Heat Resistant Material (Slate, Marble, Tile, etc.)
Above Fireplace
Noncombustible Requirements for
Material Distance (A) Safe Installation
12" or more Noncombustible material OK.
Between 8" and 12" 24" Models: Install fireplace hood ac-
cessory (GA6060, see Accessories,
page 27).
18" Model: Noncombustible mate-
rial OK.
Less than 8" Noncombustible material must be ex-
tended to at least 8". See Between 8"
and 12", above. If you cannot extend
material, you must operate heater
with flue damper open.
Minimum Noncombustible Material Clearances
If Not Using Mantel
Note: If using a mantel proceed to If Using Mantel. If not using a
mantel, follow the information on this page.
You must have noncombustible material(s) above the fireplace open-
ing. Noncombustible materials (such as slate, marble, tile, etc.)
must be at least 1/2 inch thick. With sheet metal, you must have
NOTICE: Non thermostat controlled heaters maybe used
as a vented product. If so, you must always run heater
with chimney flue damper open. If running heater with
damper open, noncombustible material above fireplace
opening is not needed. Go to Installing Damper Clamp Ac-
cessory for Vented Operataion, page 10.
INSTALLATION
Installation and Clearances for Vent-Free Operation (Cont.)
noncombustible material behind it. Noncombustible material must
extend at least 8" up (for all models). If noncombustible material
is less than 12", you must install the fireplace hood accessory (24"
and 30" Models Only). See Figure 5 for minimum clearances.
If Using Mantel
You must have noncombustible material(s) above the fireplace
opening. Noncombustible materials (such as slate, marble, tile,
etc.) must be at least 1/2 inch thick. With sheet metal, you must
have noncombustible material behind it. Noncombustible material
must extend at least 8 inches up (for all models). If noncombus-
tible material is less than 12", you must install the fireplace hood
accessory (24" Models Only). Even if noncombustible material is
more than 12", you may need the hood accessory to deflect heat
away from your mantel shelf. See Figure 5 and Figures 6 and 7,
page 9, for minimum clearances.
IMPORTANT: If you cannot meet these minimum clearances, you
must operate heater with chimney flue damper open. Go to Installing
Damper Clamp Accessory for Vented Operation, page 10.