VENTING INSTALLATION
Continued
Figure 19 - Firestop Spacer with Living
Space Above Ceiling
Figure 20 - Firestop Spacer with Attic
Space Above Ceiling
Existing
Ceiling
Frame
Firestop
Spacer
Screws or
Staples
(Min. of 8)
Firestop
Spacer
Screws or Staples
(Min. of 8)
Existing
Ceiling
Frame
Figure 21 - 10 Foot Rule
All chimney terminations must extend a mini-
mum of 3 feet above the highest point where it
passes through the roof and must be at least 2
feet above roof with a 10 foot horizontal span
(see Figure 21).
IMPORTANT: If an exposed portion of chim-
ney is greater than 4 feet above the rooine,
use support wires to keep chimney secure.
Support wires may be attached to outer pipe
of chimney with screws, if screws do not
penetrate inner ue pipe.
MINIMUM
HEIGHT
15 FT.
(4.5m)
MAXIMUM
HEIGHT
CHASE
TERMINATION
40 FT.
(12m)
Figure 22 - Maximum Chimney Height
Storm
Collar
Flashing
Firestop
Spacer
RTL-12D RTL-12D STL-12D
The minimum height of the chimney (mea-
sured from the base of the replace to the ue
gas outlet-end of pipe) is 16 feet for a straight
run, 16 feet minimum for a run with 1 elbow set
and 25 feet minimum for a run with 2 elbow
sets. (A set consists of one starter elbow and
one return elbow.)
Uncommon circumstances such as neigh-
boring hills, tall trees, or strong wind areas
can cause down drafts in chimney system.
In such cases, going beyond the minimum
recommended height would be preferable to
provide a better draw.
The replace height approved for any chim-
ney run with this replace system is 40 feet
measured from bottom of replace to ue
outlet-end of pipe (see Figure 22).
-