Figure 29 - Vertical Rigid Venting
Conguration Using Two 90° Elbows
with Two Horizontal Runs
Vertical (V) Horizontal (H)
5' min. 2' max.
6' min. 4' max.
7' min. 6' max.
8' min. 8' max.
20' max. 8' max.
Figure 30 - Vertical Rigid Venting
Conguration Using One 90° Elbow
Vertical (V
1
) Horizontal (H)
5' min. 6' max.
6' min. 12' max.
7' min. 18' max.
8' min. 20' max.
Figure 31 - Vertical Rigid Venting
Conguration Using Two 90° Elbows
VENTING INSTALLATION
INSTRUCTIONS
Continued
Figures 29 through 32 show four different congu-
rations for vertical termination. These minimum
vertical rises are based on horizontal runs with a
minimum of 1/4" upwards pitch per foot ad do
not reect constraints on a vertical system with
45° or greater offset.
Any offset pitch of 45° or less must be considered
horizontal and sized within the maximum allow-
able lengths listed in the following examples. All
connections must be sealed with high temperature
silicone sealant as specied in the second warning
statement on page 11.