Desa CGS2718PA, CGS2718NA, CGS3124PA, CGS3124NA, SGS3124PA, SGS3124NA,CLD3018PTA, CLD3018NTA, CLD3924NTB, CLD3924PTB Water Heater User Manual


 
www.desatech.com
113101-01C 15
INSTALLATION
Continued
CHECKING GAS CONNECTIONS
WARNING: Test all gas piping
and connections , internal and
external to unit, for leaks after
installing or servicing. Correct
all leaks at once.
WARNING: Never use an
open flame to check for a leak.
Apply a commercial leak de
-
tection solution to all joints.
Bubbles forming show a leak.
Correct all leaks at once.
CAUTION: For propane/LP
units, make sure external regula
-
tor has been installed between
propane/LP supply and heater.
See guidelines under Connecting
to Gas Supply, page 13.
PRESSURE TESTING GAS SUPPLY
PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG
(3.5 kPa)
1. Disconnect appliance with its appliance main
gas valve (control valve) and equipment shutoff
valve from gas supply piping. Pressures in ex-
cess of 1/2 psig will damage heater regulator.
2. Cap off open end of gas pipe where equipment
shutoff valve was connected.
3. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve
located on or near gas meter for natural gas
or using compressed air.
4. Check all joints of gas supply piping system.
Apply a commercial leak detection solution
to all joints. Bubbles forming show a leak.
5. Correct all leaks at once.
6. Reconnect heater and equipment shutoff valve
to gas supply. Check reconnected fittings for
leaks.
Test Pressures Equal To or Less Than
1/2 PSIG (3.5 kPa)
1. Close equipment shutoff valve (see Figure 15).
2. Pressurize supply piping system by either
opening propane/LP supply tank valve for
propane/LP gas or opening main gas valve
located on or near gas meter for natural gas
or using compressed air.
3. Check all joints from gas meter (natural gas) or
propane/LP supply to equipment shutoff valve
(see Figure 16 or 17). Apply a commercial
leak detection solution to all joints. Bubbles
forming show a leak.
4. Correct all leaks at once.
Figure 15 - Equipment Shutoff Valve
Equipment Shutoff Valve
Propane/LP
Supply Tank
Control Valve
Location
Figure 17 - Checking Gas Joints
(Natural Gas Only)
Gas
Meter
Equipment Shutoff Valve
Control Valve Location
Figure 16 - Checking Gas Joints
(Propane/LP Gas Only)
Open
Closed
Equipment
Shutoff Valve