WARNING: Maintain the
18", 24", 30" 16" 42"
LOG SIzING REQUIREMENTS
18" 17" 14" 24" 20"
24" 17" 14" 28" 21"
30" 17" 14" 34" 24"
* Measured at 14" depth.
Carefully follow the instructions below. This will
ensure safe installation into a masonry, UL127-
listed manufactured replace or certied vent-free
rebox.
A. Clearances from the side of the fireplace
cabinet to any combustible material and wall
should follow diagram in Figure 4.
Example: The face of a mantel, bookshelf,
etc. is made of combustible material and
protrudes 3
1
/2" from the wall. This combus-
tible material must be 4" from the side of the
replace opening (see Figure 4).
Note: When installing your gas logs into
a manufactured firebox, follow firebox
manufacturer’s instructions for minimum
clearances to combustible materials.
B. Clearances from the top of the replace opening
to the ceiling should not be less than 42 inches.
INSTALLATION
Continued
Figure 4 - Minimum Clearance for
Combustible to Wall
*Minimum 16 inches from Side Wall
Example
*
If so, you must always run heater
Installing Damper
Clamp Accessory for Vented
Operation
Note: If using a mantel, proceed to If Using
Mantel, page 10. If not using a mantel, follow the
information below.
You must have noncombustible material(s) above
the replace opening. Noncombustible materials
(such as slate, marble, tile, etc.) must be at least
1/2 inch thick. With sheet metal, you must have
noncombustible material behind it. Noncombus-
tible material must extend at least 8" up (for all
models). If noncombustible material is less than
12", you must install the replace hood accessory
(24" and 30" models only). See Figure 5, page 10
for minimum clearances.
IMPORTANT: If you cannot meet these minimum
clearances, you must operate heater with chimney
ue damper open. Go to Installing Damper Clamp
Accessory for Vented Operation, page 11.