Desa LMFP33PR(B) Indoor Fireplace User Manual


 
www.desatech.com
119526-01A 13
Figure 17 - Minimum Mantel Clearances for Built-In Installation
Supplied
Firebox
Hood
Must Be
Used at
All Times
Wire-mesh
Screen
Firebox
Noncombustible
Material May
Project Off this
Surface above
the Firebox
Hood
Mantel Shelf
13" 16" 19" 21"
2
1
/2
"
6"
8"
10"
Note: All vertical
measurements are
from top of fireplace
hood opening to
bottom of mantel
shelf. These minimum
clearances replace any
other recommended
clearances supplied
with your ANSI Z21.11.2
approved gas logs.
Wall board or facing
material (above
firebox) may be of
combustible material,
including decorative
mantel ornaments or
other similar projec-
tions off of the facing
material.
Framing
Material
INSTALLATION
Continued
INSTALLING GAS PIPING TO
FIREPLACE LOCATION
WARNING: This appliance
requires a 1/2" NPT (National
Pipe Thread) inlet connection to
the pressure regulator.
WARNING: A qualied service
person must connect replace
to gas supply. Follow all local
codes.
CAUTION: Never connect pro-
pane/LP replace directly to the
propane/LP supply. This replace
requires an external regulator
(not supplied). Install the external
regulator between the replace
and propane/LP supply.
WARNING: Never connect
natural gas replace to private
(non-utility) gas wells. This
gas is commonly known as
wellhead gas.
Installation Items Needed
Before installing replace, make sure you have
the items listed below.
external regulator for propane/LP unit only
(supplied by installer)
piping (check local codes)
sealant (resistant to propane/LP gas)
equipment shutoff valve *
test gauge connection *
sediment trap (optional)
tee joint
pipe wrench
approved exible gas line with gas connector
(if allowed by local codes) (not provided)
* A CSA design-certied equipment shutoff valve
with 1/8" NPT tap is an acceptable alternative to
test gauge connection. Purchase the optional CSA
design-certied equipment shutoff valve from your
dealer. See Accessories, page 29.