Desa CGP26D Electric Heater User Manual


 
7
101827
AIR FOR
COMBUSTION
AND
VENTILATION
Continued
Figure 2 - Ventilation Air from Inside Building
Or
Remove
Door into
Adjoining
Room,
Option 3
Ventilation Grills
Into Adjoining Room,
Option 2
12"
12"
Ventilation
Grills
into Adjoining
Room,
Option 1
Continued
WARNING ICON G001
WARNING
If the area in which the heater may be operated is smaller than
that defined as an unconfined space, provide adequate combus-
tion and ventilation air by one of the methods described in the
National Fuel Gas Code, ANSI Z223.1, 1992, Section 5.3.
VENTILATION AIR
Ventilation Air From Inside Building
This fresh air would come from an adjoining unconfined space. When ventilat-
ing to an adjoining unconfined space, you must provide two permanent
openings: one within 12" of the ceiling and one within 12" of the floor on the
wall connecting the two spaces (see options 1 and 2, Figure 2). You can also
remove door into adjoining room (see option 3, Figure 2). Follow the National
Fuel Gas Code NFPA 54/ANSI Z223.1, Section 5.3, Air for Combustion and
Ventilation for required size of ventilation grills or ducts.
WARNING ICON G001
WARNING
Rework worksheet, adding the space of the adjoining unconfined
space.
The combined spaces must have enough fresh air to supply all
appliances in both spaces.