Denso CLASSIC PLUS 26 Air Conditioner User Manual


 
18
TECHNICAL SPECIFICATIONS
MODEL
ITEM/FEATURES Classic Plus 14 Classic Plus 26
Rating Conditions
dry bulb 95
o
F (35
o
C) 95
o
F (35
o
C)
wet bulb 83
o
F (28.3
o
C) 83
o
F (28.3
o
C)
humidity (60%) (60%)
Specifications
power frequency 60Hz 60Hz
line voltage, single phase 115 V 208/230V
power consumption 1.41 Kw 3.37/3.24 Kw
current consumption 12.3 Amps 16.8/14.6 Amps
power factor 95% 97%
starting current 32A 62A
power cord 14 (3-core) AWG 12 (3-core) AWG
Cooling Unit
cooling capability 3,300 Kcal/hr 6,500 Kcal/hr
13,200 BTU/hr 26,000 Btu/hr
cooling system direct expansion direct expansion
Blower
type of fan centrifugal fan centrifugal fan
air volume:
Evaporator (high speed)
470 ft
3
/min;798 m
3
/h 708 ft
3
/min; 1202 m
3
/h
Condenser (high speed)
882 ft
3
/min;1498 m
3
/h 1680 ft
3
/min; 2853 m
3
/h
motor output: (high speed) 0.24 Kw .59/.63 Kw
(low speed) 0.19 Kw .54/.56 Kw
Compressor
type rotary hermetic scroll
output 0.8 Kw 1.6kw
refrigerant type R-22 R-22
refrigerant capacity 1.50 lbs (0.68 kg) 1.87 lbs. (0.85 kg)
Safety Devices
compressor overload protector
included included
fan motor protector
included included
anti-freezing thermistor
included included
full drain tank switch
included included
automatic restart (power interruption)
included included
compressor time delay program
included included
Dimensions & Weight
W x D x H (in.) 19.4 x 26.5 x 41.5 19.4 x 28.7 x 47.2
W x D x H (mm) 492 x 673 x 1054 492 x 730 x 1200
weight (lbs/kg) 165/75 235/107
Operating Conditions
inlet air (relative humidity) 113
o
F (45
o
C), < 50% 113
o
F (45
o
C), < 50%
70
o
F (21.1
o
C), > 50% 70
o
F (21.1
o
C), > 50%
Control Device
temperature control included included
two speed fan included included