Dayton 3VH34 Electric Heater User Manual


 
Key
Infra-red heater
Exhauster
Thermostat
Air intake louver
Perimeter mounting
A
B
C
Perimeter and center row mounting
A
B
Dayton Installation, Operation, Maintenance and Parts Manual
Dayton High Intensity Heaters
®
3E132 thru 3E134, 3E460 thru 3E462,
5VD57 thru 5VD66, 3VH34 thru 3VH37
E
N
G
L
I
S
H
10
Chart 2.1 - Recommended Mounting Heights and Distances for “Total Area” Heating
Figure 2.1 - Total Area Heating Sample Layout
BTU/H Input
Distance
Between
Heaters
Dim. B (ft.)
Distance
Between
Heater Rows
Dim. C (ft.)
Distance
Between
Heater
and Wall (ft.)
30,000 12-14 12-15 8-30 10-70 6
60,000 14-16 18-21 15-43 15-90 12
90,000 16-18 21-25 20-55 20-110 12
Mounting Heights Dim. A
30º Angle
Standard
Reflector (ft.)
30º Angle
Parabolic
Reflector (ft.)
Factory recommended mounting heights are listed as a guideline. If infra-red heaters are mounted too low or too
high, they may result in discomfort or lack of heat. The factory generally recommends observing the recommended
mounting heights to optimize comfort conditions. However, certain applications such as spot heating, freeze
protection, outdoor patio heating or very high ceilings may result in the heaters being mounted outside of the
recommended mounting heights.