Crown Boiler ODV-100 Boiler User Manual


 
1919
IXStart-upandCheckout
Use the following procedure for initial start-up of the boiler:
1) Make sure that the boiler and system are lled with water.
2) Check all system and fuel piping for leaks. Repair any leaks found immediately.
3) Vent system must be complete and free of obstructions before attempting to re boiler. Do not
re boiler until all vent sealant has had at least one hour to cure.
4) Inspect all line voltage wiring for loose or un-insulated connections.
5) If the boiler is connected to a one-pipe system, purge the suction line in accordance with the
instructions supplied with the pump.
WARNING
If antifreeze is used in the system, it must be a nontoxic type such as propylene
glycol.
Never attempt to ll a hot empty boiler
Make sure that the area around the boiler is clear and free from combustible
materials, gasoline, and other ammable vapors and liquids.
CAUTION
Safe reliable operation of this boiler requires that the burner be checked and
adjusted by a qualied oil serviceman using combustion test instruments
Do not drill a hole in the vent system to take combustion gas samples. Take
combustion gas samples through the bolthole on the top of the 7 x 4 adapter.