Crown Boiler BWC300 Boiler User Manual


 
3
Table 1.1: Summary of PPs Flex Venting Options
VENT OPTION # 9 10
CLASSIFICATION USED IN THIS MANUAL
PPs FLEX
(MASONRY)
PPs FLEX
(MASONRY)
ILLUSTRATED IN FIGURE 1.0 1.0
VENT PIPE PENETRATION THROUGH STRUCTURE CHIMNEY CAP CHIMNEY CAP
AIR INTAKE PENETRATION THROUGH STRUCTURE CHIMNEY CAP CHIMNEY CAP
MIN CHASE ID (ROUND)
6” DIA 7” DIA
MIN CHASE ID (RECTANGULAR)
6” x 6” 7” x 7”
NOMINAL PPs FLEX LINER SIZE
80 mm 100mm
CONCENTRIC VENT/INTAKE CONNECTOR SIZE
80/125 100/150
MAXIMUM TOTAL VENT LENGTH
(INLUDING PPS FLEX IN CHASE)
VENT
BWC070 51ft
BWC090 51ft
BWC120 51ft
BWC151 51ft
BWC150 47ft
BWC225 45ft
BWC300 68ft
INLET
BWC070 51ft
BWC090 51ft
BWC120 51ft
BWC151 51ft
BWC150 47ft
BWC225 45ft
BWC300 68ft
MAX CHASE HEIGHT
32ft 32ft
CROWN PPs FLEX LINER PART # (32ft COIL) 230955 230956
CROWN PPs FLEX INSTALLATION KIT PART # 230958 230959