Crestron electronic 1.5 Boiler User Manual


 
7
Installation & Operation Manual
Installation must comply with:
Local, state, provincial, and national codes, laws,
regulations, and ordinances.
National Fuel Gas Code, NFPA 54 / ANSI Z223.1 –
latest edition.
Standard for Controls and Safety Devices for
Automatically Fired Boilers, ANSI/ASME CSD-1 -
latest edition, when required.
National Electrical Code, NFPA 70 - latest edition.
• For Canada only: CSA B149.1 Installation Code,
CSA C22.1 Canadian Electrical Code Part 1 and any
local codes.
ƽ WARNING
This appliance is certified as an indoor appliance.
Do not install the appliance outdoors or locate
where the appliance will be exposed to freezing
temperatures or to temperatures that exceed 100°F
(37.8°C).
Do not install the appliance where the relative
humidity may exceed 93%. Do not install the
appliance where condensation may form on
the inside or outside of the appliance, or where
condensation may fall onto the appliance.
Failure to install the appliance indoors could result
in severe personal injury, death, or substantial
property damage.
1 Determine boiler location
The Crest gas manifold and
controls met safe lighting and other
performance criteria when the boiler
underwent tests specified in ANSI
Z21.13/CSA 4.9 – latest edition.
Before locating the boiler, check:
1. Check for nearby connection to:
• System water piping
• Venting connections
• Gas supply piping
• Electrical power
2. Locate the appliance so that if water connections
should leak, water damage will not occur. When
such locations cannot be avoided, it is
recommended that a suitable drain pan, adequately
drained, be installed under the appliance. The
pan must not restrict combustion air flow. Under no
circumstances is the manufacturer to be held
responsible for water damage in connection with
this appliance, or any of its components.
3. Check area around the boiler. Remove any
combustible materials, gasoline and other
flammable liquids.
This appliance requires a special venting system.
Use only the vent materials specified in this
manual. Failure to follow all instructions can
result in flue gas spillage and carbon monoxide
emissions, causing severe personal injury or death.
NOTICE
ƽ WARNING
Failure to keep boiler area clear
and free of combustible materials,
gasoline, and other flammable
liquids and vapors can result in
severe personal injury, death, or
substantial property damage.
4. The Crest must be installed so that gas control
system components are protected from dripping or
spraying water or rain during operation or service.
5. If a new boiler will replace an existing boiler, check
for and correct system problems, such as:
• System leaks causing oxygen corrosion or heat
exchanger cracks from hard water deposits.
• Incorrectly-sized expansion tank.
• Lack of freeze protection in boiler water causing
system and boiler to freeze and leak.
6. The appliance must be installed on a level floor,
both front to back and side to side, for proper
condensate drainage.
Provide clearances:
Clearances from combustible materials
- Hot water pipes ........................................................ 1/4"
- Sides .......................................................................... 0"
- Rear ........................................................................... 0"
- Front ......................................................................... 0"
- Top ........................................................................... 0"
- Floor ....................................................... Combustible
- Vent pipe - Follow special vent system manufacturer’s instructions
Recommended clearances for service access
- Sides .......................................................................... 24"
- Rear ........................................................................... 24"
- Front ......................................................................... 30"
- Top ........................................................................... 24"
ƽ WARNING
1/4" (6 MM) MINIMUM CLEARANCE
AROUND HOT WATER PIPES
VENTILATING*
AIR OPENING
VENTILATING*
AIR OPENING
CLOSED DOOR
24"
LEFT
24"
RIGHT
24"
TOP
30"
FRONT
24"
REAR
Figure 1-1 Recommended Service Clearances
If you do not provide the recommended service
clearances shown, it may not be possible to service
the boiler without removing it from the space.
NOTICE