Conair VL Series Air Conditioner User Manual


 
Page: 39
UGH020/0301 VL Series Portable Chillers, 0.25 to 1.5 Tons
8.5 CHILLER CAPACITY AND DERATE CHART
60
50
45
40
35
30
25
20
15
10
5
0
-5
*
*
*
*
*
105%
100%
90%
80%
70%
60%
50%
40%
30%
22%
15%
9%
5%
OUTPUT
TEMPERATURE
°F
FULL
AVAILABLE %
CAPACITY
NOTES:
If operation of the chiller at less than 48°F is
required, an inhibited propylene glycol
solution is required.
Consult factory for chiller operation below
20°F.
Ambient conditions affect air cooled chiller
operation and capacity. Standard rating is at
95°F entering air temperature. For ambient
air conditions greater than 95°F, chiller
derating will occur. For ambient temperatures
of 95-105°F, select the next larger capacity
chiller. For ambient temperatures over 105°F,
consult factory.
* These ranges require special options.
Standard chiller rating is at 50°F. For all other temperature settings,
output tonnage is altered as follows: