VL Series Portable Chillers, 0.25 to 1.5 Tons UGH020/0301
8.1 SPECIFICATIONS
VL Air-cooled Portable Chillers: 0.25 to 1.5 tons
SPECIFICATION NOTES
* Ton capacity at 12,000 BTU/ton @ 50°F leaving water temperature @ 115°F condensing temperature. Capacities
may be ± 5% as reserved by the compressor manufacturer. Capacity multipliers are: 50°F - 1.00; 40°F - 0.80;
30°F - 0.60; 20°F - 0.40.
Hermetic reciprocating compressor.
Consult pump curve for exact characteristics relating to pump performances.
§
Unit weight crated for shipment
** No allowance for inrush. Service disconnect by owner. Full load amps must be used to size disconnects and
supply conductors. Consult factory for 50hz operation.
Specifications can change at any time. Contact your Conair representative for the most current information.
MODEL VLA-.25 VLA-.33 VLA-.5 VLA-.75 VLA-1 VLA-1.5
Performance characteristics
Capacity* tons 0.25 0.32 0.41 0.70 0.98 1.35
Compressor Hp {kW}
0.25 {0.19} 0.33 {0.25} 0.5 {0.37} 0.75 {0.56} 1 {0.75} 1.5 {1.1}
Pump Hp {kW} 0.25 {0.19} 0.25 {0.19} 0.25 {0.19} 0.25 {0.19} 0.5 {0.37} 0.5 {0.37}
Chilled water flow
gpm {lpm} 0.6 {2.3} 0.8 {3.0} 0.9 {3.4} 1.7 {6.4} 2.4 {9.1} 3.6 {13.6}
Chilled water pressure
psi {bar} 60 {4.1} 60 {4.1} 60 {4.1} 60 {4.1} 60 {4.1} 60 {4.1}
Reservoir capacity gal {liters} 4 {15} 4 {15} 4 {15} 4 {15} 4 {15} 4 {15}
Dimensions in {mm}
Height 33 {838} 33 {838} 33 {838} 33 {838} 33 {838} 37 {940}
Width 18 {457} 18 {457} 18 {457} 18 {457} 18 {457} 19 {483}
Depth 24 {610} 24 {610} 24 {610} 24 {610} 24 {610} 25 {635}
Pipe size NPT in.
Process (to and from) 0.5 0.5 0.5 0.5 0.5 0.75
Condenser
Weight lb {kg}
Shipping
§
150 {68} 150 {68} 170 {77} 205 {93} 210 {95} 220 {100}
Voltages full load amps**
115V/1 phase/60Hz 11 12 14 22 24
220V/1 phase/60Hz 8 11 12 15
Refrigerant HCFC-22