Coleman FC8T Furnace User Manual


 
036-21603-002 Rev. A (1004)
Unitary Products Group 3
Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.
Wire size and over current protection must comply with the National Electrical Code (NFPA-70-latest edition) and all local codes.
The furnace shall be installed so that the electrical components are protected from water.
* ESP (External Static Pressure) .5" WG is at furnace outlet ahead of cooling coil.
NOTES:
1. All filters must be high velocity cleanable type.
2. Air flows above 1800 CFM require either return from two sides or one side plus bottom.
RATINGS & PHYSICAL / ELECTRICAL DATA
Model
Output Nominal
Cabinet
Width
AFUE
Air Temp. Rise
Max. Outlet
Air Temp.
MBH CFM In. °F °F
(F,L)C8T060A12UH11
46/34 1200 14-1/2 80.0 25-55 165
(F,L)C8T080A12UH11
64/48 1200 14-1/2 80.0 30-60 175
(F,L)C8T080B16UH11
64/48 1600 17 1/2 80.0 25-55 160
FC8T100B12UH11
80/53 1200 17 1/2 80.0 25-55 170
(F,L)C8T100C20UH11
80/53 2000 21 80.0 25-55 160
FC8T120C16UH11
96/64 1600 21 80.0 25-55 180
(F,L)C8T120C20UH11
96/64 2000 21 80.0 25-55 170
Model
Output Blower
Blower
Size
Total
Unit
Max Over-current
Size (awg) @
75 ft.protect
Min.
Wire
one way
Operation
WGT.
MBH Hp Amps In. Amps LBS
(F,L)C8T060A12UH11
46/34 1/3 6.2 10 x 7 9.0 20 14 107
(F,L)C8T080A12UH11
64/48 1/3 6.2 10 x 7 9.0 20 14 119
(F,L)C8T080B16UH11
64/48 3/4 11.5 11 x 8 12.0 20 14 129
FC8T100B12UH11
80/53 1/2 7.0 10 x 8 12.0 20 14 131
(F,L)C8T100C20UH11
80/53 1.0 12.2 11 x 10 14.0 20 12 149
FC8T120C16UH11
96/64 1/2 10.4 10 x 10 12.0 20 14 149
(F,L)C8T120C20UH11
96/64 1.0 12.2 11 x 10 14.0 20 12 151
FILTER SIZES
Cabinet Size Side (in) Bottom (in)
A 16 x 26 14 x 26
B 16 x 26 16 x 26
C (2) 16 x 26 20 x 26
D (2) 16 x 26 20 x 26