Vermont Casting SC36 Indoor Fireplace User Manual


 
12
Majestic Fireplaces® SR/SC Series
Continue installing the pipe as required until pipe is
installed up through the ceiling. At this point, you must
install a firestop spacer.
Installing the Firestop Spacer
in the Ceiling Hole
A firestop spacer is used to keep pipe spaced properly
and required for safety.
Nail the firestop spacer (at each corner) to the framing
members of the ceiling hole. Note: A firestop spacer is
not required at the roof.
Hole sizes listed in Figure 13 for angled firestop
spacers provide minimum required air space to chim-
ney pipe for ceiling thickness up to eight (8) inches.
When combined thickness of ceiling material, ceiling
joists and flooring material exceeds eight (8) inches,
adjustments must be made in framing to assure that
minimum air spaces to chimney are maintained.
Proper Firestop Spacer Installation
Figure 18 shows different installation procedures for
both an area that
is
an attic and an area that
is not
an
attic.
If the area above the ceiling is not an attic, position the
firestop spacer with the flange on the ceiling side and
the angled portion extending up into the hole.
If the area above the ceiling is an attic, position the
firestop spacer with the flange on the top of the framed
hole and the angled portion extending down into the
hole.
Firestop spacers are not available for nor are they
required on vertical walls.
DO NOT put any sealant around the area where the
outer pipe slides through the firestop spacer. If you
seal this area, it may cause a fire hazard.
Canadian Requirements
for Insulation Shield
In Canada, an attic
insulation shield is
required to prevent attic
insulation from contact-
ing the chimney sec-
tion. Framing dimen-
sions for the chimney
hole should measure
14¹⁄₂" x 14¹⁄₂". An attic
shield MUST be in-
stalled on top of attic
joists (above the floor
level). (Fig. 19)
Fig. 18 Installing firestop spacer.
FP593
FP558
Fig. 16 Install pipe, listening for the snap-lock to fasten.
UP
LANCE
HEM
PIPE RIM
PIPE
RIM
PIPE SECTION
JOIST
NAILS (4)
FIRESTOP
SPACER
JOIST
NAILS (4)
FIRESTOP
SPACER
Ceiling InstallationAttic Installation
ELBOW STRAP
ANGLED STRAP
Fig. 17 Attach straps to a structural framing member.
FP270/271
SUPPORT
STRUCTURE
ELBOW
STRAP
(must be tight)
CHIMNEY
SUPPORT
STRAP
(must be tight)
CEILING
HOLE
FRAMING
ANGLE
FIRESTOP