Century CB00001 Stove User Manual


 
Century S244 Installation and Operation Manual
32
7.4.2 Table of Clearance Reduction Percentages
Type of shield
Clearances may be
reduced by these
percentages
Sides
and rear %
Top %
(ceiling)
Sheet metal, a minimum of 24
gauge (0.61 mm) in thickness ,
spaced out at least 25 mm (1 in)*
by non-combustible spacers
67 50
Ceramic tiles, or equivalent non-
combustible material, on non-
combustible board spaced out at
least 25 mm (1 in)* by non-
combustible spacers
50 33
Ceramic tiles, or equivalent non-
combustible material, on non-
combustible board, with a
minimum of 24 gauge (0.61
mm)
sheet metal backing spaced out at
least 25 mm (1 in)* by non-
combustible spacers
67 50
Brick, spaced out at least 25 mm
(1 in)* by non-combustible spacers
50 N/A
Brick, with a minimum of 24 gauge
(0.61 mm) sheet metal backing,
spaced out at least 25 mm (1 in)*
by non-combustible spacers
67 N/A
* In Canada this space can be 21 mm (7/8 in)