Carrier TP-NHP Thermostat User Manual


 
30
becomes brighter when a button is pressed. After 10 seconds of no button
presses, the backlight will return to the dimmer level until another button press
occurs. The range of brightness is 1 through 5 with 5 being full brightness.
Default is 3.
Option 19 — Dry Contact Configuration (programmable models only)
There are 2 available selections, OF and 1.
OF — The dry contact is always deenergized.
1 — The dry contact will be energized for the specified number of minutes per
hour. This selection is programmable by period. When this selection is changed
from OF to 1, the period icons are shown and the minute segments of the clock
display are shown. The triangle icon next to the WAKE period will be on and a
value between 0 and 60 will be shown in the minutes display. See Operational
Information and Wiring Diagrams for further explanation of dry contact
configuration and use. To change the period or minutes, press the soft key below
the period or minutes and then use the UP/DOWN buttons to change to the
desired value.
Default is OF (off).
Option 20 — Outdoor Air Temperature Offset Adjustment
This selection allows the calibration, or deliberate miscalibration of the outdoor
air temperature sensor reading. The selection ranges from 5 to +5_.
Default is 0.
Option 21 — Keypad Lockout (programmable models only)
This selection allows the installer to limit access to the keypad. Selections are OF
(off), 1, 2, 3.
OF (off) — The user has full access to the keypad.