Fig. 13—Service Label
A93297
- Stuck gas valve relay on control or miswire to gas valve circuit.
- Stuck-open gas valve or leaky gas valve.
- Obstructed pressure tubing.- Defective pressure switch (stuck closed).
- Short circuit in secondary voltage (24V) wiring.
- Proper vent sizing and condensate pitch. - Inadequate combustion air supply.
- Vent restriction or high winds. - Low inducer voltage.
- Defective inducer motor or start capacitor.
- Defective pressure switch or connections. If it opens after trial for ignition
period, blower will come on for 90 second recycle delay.
- Disconnected or obstructed pressure tubing.
- Defective blower motor or start capacitor. - Dirty filter or restricted duct system.
- Loose blower wheel. - Defective switch or connections.
- Inadequate combustion air supply (flame rollout switch only).
- Open flame rollout switch, manual reset.
- Oxide buildup on flame sensor (clean with fine sandpaper).
- Proper flame sense microamps (.5 microamps D.C. minimum).
- Gas valve turned off. - Manual shut-off valve.
- Green wire MUST be connected to furnace sheet metal.
- Inadequate flame carryover or rough ignition.
- Low inlet gas pressure.
SERVICE
COMPONENT TEST
1
2
3
456
7
8
9
STATUS
TEST
HUM C W Y R G
320615-102 REV. A
To initiate the component test sequence, shut OFF the room thermostat or disconnect the "R"
thermostat lead. Briefly short the TEST terminal to the "C" terminal. Status LED will flash code
and then turn on the inducer motor, hot surface igniter, blower motor-heat speed, and blower
motor-cool speed for 10-15 seconds each.
BLOWER OFF
DELAY SELECT
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST
DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT
BY THE NUMBER OF LONG FLASHES.
LED CODE
CONTINUOUS OFF 
CONTINUOUS ON
RAPID FLASHING
- Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.
- Control has 24V power.
- Line voltage (115V) polarity reversed. If twinned, 24V power to
one furnace may be out of phase with 24V power to other furnace.
STATUS
11
12
13
14
21
22
23
24
31
33
34
NO PREVIOUS CODE - Stored status codes are erased when power (115V or 24V) to
control is interrupted or 48 hours after each fault is cleared.
BLOWER ON AFTER POWER UP (115V OR 24V) - Blower runs for 90 seconds, if unit
is powered up during a call for heat (R-W closed).
LIMIT OR FLAME ROLLOUT SWITCH LOCKOUT - Auto reset after three hours. Flame
rollout switch requires manual reset. Refer to #33.
IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for:
ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is 
de-energized. Inducer will run until fault is cleared.
Check for:
PRESSURE SWITCH DID NOT OPEN Check for:
SECONDARY VOLTAGE FUSE IS OPEN
Check for:
PRESSURE, DRAFT SAFEGUARD, OR AUXILIARY LIMIT (when used) SWITCH DID
NOT CLOSE OR REOPENED - If open longer than five minutes, inducer shuts off for
15 minutes before retry. Check for:
LIMIT OR FLAME ROLLOUT SWITCH IS OPEN - If open longer than three minutes, code
changes to #13. Check for:
IGNITION PROVING FAILURE - Control will try three more times before a lockout #14
occurs. If flame signal lost after trial for ignition period, blower will come on for 90 second
recycle delay.
Check for:
SERVICE LABEL
9