Carrier 50EJ Air Conditioner User Manual


 
Step 6 Controls Options The control options
that the units can provide are based on the following param-
eters: CV (constant volume) or VAV (variable air volume)
operation; stand-alone unit with field-supplied sensors in-
stalled (CV or VAV); as a system via the Carrier Comfort
System (TEMP or VVT); optional electronic expansion board
installed (CV or VAV); linked to the Carrier Comfort Net-
work; and availability of a computer and software (Comfort
Works, Building Supervisor, and Service Tool) to access the
base control board. See Table 3.
NOTE: Access to the base control board allows unit occu-
pancy schedules, unit timeclock, and various set points to be
changed from their factory-defined default settings.
CONSTANT VOLUME APPLICATIONS The standard
CV unit is capable of being operated with either a Carrier-
approved thermostat or a field-supplied sensor. (See Price
Pages for ordering information.)
Features with Thermostat Control of Unit
two-stage heating (if installed)
two-stage cooling
control of unit using Y1, Y2, W1, W2, and G thermostat
inputs
control of the indoor fan
outdoor air temperature/supply air temperature monitoring
control of an outdoor air condenser fan based on outdoor
air temperature
control of modulating economizer damper to provide free
cooling when outdoor conditions are suitable, using sup-
ply air temperature as a control point
control of the economizer damper and indoor fan to obtain
unoccupied free cooling
provide power exhaust output to an external power ex-
haust controller
support a field test for field checkout
control of 2 stages of CV power exhaust
compressor Time Guard (power up and minimum off and
on times)
Additional features are provided by accessing the stand-
ard unit control board via software with a computer. These
features are:
electronic expansion board features (if installed)
compressor lockout during low supply air temperature
control board diagnostics
ability to change supply air set point (economizer control)
ability to change high outdoor air temperature lockout set
point (economizer control)
ability to change power exhaust set points
NOTE: A CV unit without a thermostat requires a field-
supplied sensor for operation.
Features with Sensor Control of Unit (Stand-Alone Appli-
cations Unit control is limited to CV unoccupied default
set points, 90 F for cooling, 55 F for heating. There are
3 sensor options available:
T-57 sensor will monitor room temperature
T-55 sensor will monitor room temperature and provide
unoccupied override capability (1 hour)
T-56 sensor will monitor room temperature, provide un-
occupied override capability (1 hour), and provide a tem-
perature offset of F.
Standard features are:
support of remote occupied/unoccupied input to start and
stop the unit
cooling capacity control of 3 stages using economizer and
2 compressors to maintain space temperature to an occu-
pied or unoccupied set point
enable heating (if installed) or cooling during unoccupied
periods as required to maintain space temperature within
the unoccupied set points
adjustment of space temperature set points of ± 5° F when
using a T-56 sensor
Table 3 Controls Options and Configurations (Non-Thermostat Applications)
UNIT CONFIGURATION DEFAULT COOLING DEFAULT HEATING
UNITS RUNNING VERSION 1.0 UNIT CONTROL SOFTWARE
CV or VAV Unit with SPT Sensor
Unoccupied Cooling — 90 F (SPT)
Occupied Cooling NA
Unoccupied Heating — 55 F (SPT)
Occupied Heating NA
CV Unit with SPT Sensor and Remote
Start/Stop Switch
Unoccupied Cooling — 90 F (SPT)
Occupied Cooling 78 F (SPT)
Unoccupied Heating — 55 F (SPT)
Occupied Heating 68 F (SPT)
VAV Unit Remote Start/Switch Only
Unoccupied Cooling — NA
Occupied Cooling 55 F (SAT)
Unoccupied Heating — NA
Occupied Heating NA
VAV Unit with SPT Sensor and Remote
Start/Stop Switch
Unoccupied Cooling — 90 F (SPT)
Occupied Cooling 55 F (SAT)
Unoccupied Heating — 55 F (SPT)
Occupied Heating NA
UNITS RUNNING VERSION 2.0 UNIT CONTROL SOFTWARE
CV or VAV Unit with SPT Sensor
Unoccupied Cooling — 90 F (SPT)
Occupied Cooling NA
Unoccupied Heating — 55 F (SPT)
Occupied Heating NA
CV Unit with SPT Sensor and Remote
Start/Stop Switch
Unoccupied Cooling — 90 F (SPT)
Occupied Cooling 78 F (SPT)
Unoccupied Heating — 55 F (SPT)
Occupied Heating 68 F (SPT)
VAV Unit Remote Start/Stop Switch Only
Unoccupied Cooling — 90 F (RAT)
Occupied Cooling 55 F (SAT)
Unoccupied Heating — 55 F (RAT)
Occupied Heating 68 F (RAT)*
VAV Unit with SPT Sensor and Remote
Start/Stop Switch
Unoccupied Cooling — 90 F (SPT)
Occupied Cooling 55 F (SAT)
Unoccupied Heating — 55 F (SPT)
Occupied Heating 68 F (RAT)*
LEGEND
CV Constant Volume SAT Supply-Air Temperature
NA Not Available SPT Space Temperature
RAT Return-Air Temperature VAV Variable Air Volume
*With DIP Switch No. 5 configured to OPEN (Occupied Heat Enabled).
NOTE: Space temperature sensor and remote stop/switch are field-supplied.
Fig. 10 Condensate Drain Connections
(Typical Roof Curb or Slab Mount Shown)
12