Carrier 50AH Air Conditioner User Manual


 
9
ELECTRIC HEATER STATIC PRESSURE DROP (in. wg)
NOTE: Above electric heaters are
not
UL (Underwriters’ Laboratories) or CSA (Canadian Standards Association)
listed for use with optional high-static evaporator-fan motor (048, 060 units only).
Controls
Operating sequence
Cooling — Thermostat calls for cooling. Indoor (evapora-
tor) fan relay is energized and starts evaporator fan. Com-
pressor contactor is energized to start compressor and
condenser fan (up to a 5-minute delay on single-phase
units). When room thermostat is satisfied, the evaporator
fan, compressor, and condenser fan shut off.
Continuous fan operation — The thermostat can be
set for continuous operation by setting the fan switch to
ON.
Electrical data
LEGEND
*Optional evaporator-fan motor nameplate data.
ELECTRIC HEATER
UNIT 88EN
UNIT
50AH
MIN
CFM
UNIT CFM
600 800 1000 1200 1400 1600 1800 2000 2200
0500CA01
024, 036
1-stage
heat
400.02.04.06.10—————
0075CA01 510.03.06.10.16—————
0115CA01 620
.04.08.13.19—————
0075EA01 320
1150EA01 720
0100EA01
048, 060
2-stage
heat
970
.04 .06 .08 .12 .15 .17
0150EA01 1240
0200EA01 1350
.08 .11 .14 .18 .22 .26
0300EA01 1220
0300CA01 1220
0100FA01 1130
.04 .06 .08 .12 .15 .17
0150FA01 1360
0200FA01 1350
.08 .11 .14 .18 .22 .26
0300FA01 1270
UNIT
50AH
V-PH
(60 Hz)
VOLTAGE RANGE COMPRESSOR
FAN MOTORS POWER SUPPLY
Evaporator Condenser
Min Ckt
Amps
MOCP
Amps
Min Max RLA LRA Hp FLA Hp FLA
024 230-1 207 254 11.4 56 .17 1.10 .50 3.40 19.0 25
036
230-1 207 254 17.2 96 .50 3.20 .75 6.06 29.5 40
208/230-3 187 254 10.3 77 .50 3.20 .75 3.93 19.9 25
460-3 414 508 5.1 40 .50 1.50 .75 1.97 8.9 15
048
230-1 207 254 24.4 150 .75 4.00 1.0 8.35 42.9 60
208/230-3 187 254 15.5 105 .75 4.00 1.0 3.93 27.3 35
460-3 414 508 7.4 55 .75 2.15 1.0 1.97 13.4 20
048*
208/230-3 187 254 15.5 105 1.5 5.60 1.0 3.93 28.9 35
460-3 414 508 7.4 55 1.5 2.80 1.0 1.97 16.3 20
060
230-1 207 254 28.8 169 .75 4.00 1.5 9.50 49.5 60
208/230-3 187 254 17.3 123 .75 4.00 1.5 4.82 30.4 40
460-3 414 508 9.0 62 .75 2.15 1.5 2.41 15.8 20
060*
208/230-3 187 254 17.3 123 1.5 5.60 1.5 4.82 32.0 40
460-3 414 508 9.0 62 1.5 2.80 1.5 2.41 16.0 20
HACR Heating, Air Conditioning, and Refrigeration
Hp Horsepower
FLA Full Load Amps
LRA Locked Rotor Amps
MOCP Maximum Overcurrent Protection (HACR breaker)
RLA Rated Load Amps