Your combination heating/cooling unit is equipped with
an automatic direct spark ignition and power combustion blower.
Do not attempt to light by hand; personal injury may
result.
TO LIGHT UNIT
1. Do not turn off the electrical power to unit without
first turning off the gas supply.
2. Before attempting to start the gas heating section, fa-
miliarize yourself with all the procedures that must
be followed.
If you do not follow these instructions exactly, a fire or
explosion may result, causing property damage, injury,
or loss of life.
Refer to Fig. 1. See Fig. 2 for location of gas valve. Refer
to Fig. 3 while proceeding with the following steps.
Step 1 — Set the temperature selector on room thermo-
stat to the lowest temperature setting and set system switch
to HEAT.
Step 2 — Close the external manual shutoff valve.
Step 3 — Turn off the electrical supply to the unit.
Step 4 — Remove the burner access panel with a
5
⁄
16
-in.
nut driver.
Step 5 — Turn the control switch on the internal gas valve
to the OFF position and wait 5 minutes.
Step 6 — Turn the control switch on the internal gas valve
to the ON position.
Step 7 — Replace the burner access panel.
Step 8 — Turn on the electrical supply to unit.
Step 9 — Open the external manual shutoff valve.
Step 10 — Set the temperature selector on room thermo-
stat slightly above room temperature to start unit. The induced-
draft combustion-air fan will start. Main gas valve will open
and main burners should ignite within 5 seconds. If the burner
does not light within 5 seconds, the ignition module will go
into a Retry mode after a period of approximately 22 sec-
onds (following the 5-second ignition period).
If the burners do not light within 15 minutes of the initial
call for heat, there is a lockout.
Step 11 — Set the temperature selector on room ther-
mostat to desired setting.
1. If the main burners fail to light, or the blower fails
to start, shut down gas heating section and call your
dealer for service.
2. Never attempt to manually light the main burners on
unit with a match, lighter, or any other flame. If the
electric sparking device fails to light the main burn-
ers, refer to the following shutdown procedures, then
call your dealer as soon as possible.
Failure to follow these requirements could result in serious
personal injury.
TO SHUT UNIT OFF
Do not turn off the electrical power to unit without first
turning off the gas supply.
Failure to follow these procedures can result in serious
fire or personal injury.
NOTE: If unit is being shut down because the heating sea-
son has ended, make sure to turn on power to cooling
system.
If unit is being shut down because of a malfunction, call
your dealer as soon as possible.
Should overheating occur or the gas supply fail to shut
off, shut off the manual gas valve to the unit before shutting
off the electrical supply.
Do not use this unit if any part has been under water. Im-
mediately call a qualified service technician to inspect the
unit and to replace any part of the control system and any
gas control which has been under water.
Refer to Fig. 4 while proceeding with the following steps.
Step 1 — Set the temperature selector on room thermo-
stat to lowest temperature setting and set system switch to
OFF.
Step 2 — Close the external manual shutoff valve.
Step 3 — Turn off the electrical power supply to the unit.
Step 4 — Remove the burner access panel.
Step 5 — Turn the control switch on the internal gas valve
to the OFF position.
Step 6 — Replace the burner access panel.
Step 7 — Restore electrical power to the unit and set sys-
tem switch to COOL to ensure operation of the cooling sys-
tem during the cooling season.
BURNER
ACCESS PANEL
Fig. 1 — Gas Heating/Electric Cooling Unit
(Unit 48SS Shown)
2