3
Table 3 — Motormaster V Control Package Contents — 48/50P070-100 Units
Table 4 — Motormaster V Control Package Usage
INSTALLATION
Pre-Installation —
Inspect the contents of this accessory
package before installing. File a claim with the shipper if there
is shipping damage or if a part is missing.
Step 1 — Install Field-Fabricated Wind Baffles
On size 040-060 units, in areas with prevailing winds of
more than 5 mph (8 kph) and where temperatures drop below
32 F (0° C), wind baffles must be field fabricated to ensure
proper cooling cycle operation at low-ambient temperatures
with Motormaster V controls. Wind baffles are not needed on
size 030, 035, and 070-100 units. See Fig. 2 for baffle details.
Use 20-gage (1 mm) galvanized sheet metal, or similar corro-
sion-resistant material for the baffles. Use field-supplied screws
to attach baffles to unit. Screws should be
1
/
4
-in. (6.3 mm) diam-
eter or larger. Screws should not be more than
1
/
2
-inch in length.
Drill required screw holes for mounting baffles.
ITEM CRLOWAMB036A00 CRLOWAMB037A00 CRLOWAMB038A00
Connector (
1
/
2
-in.) HW60EA001 (2)
Connector (1-in.) HW60HH006 (2)
Controller, 230 V 2 Hp HR46TN001 (2) — —
Controller, 460 V 2 Hp — HR46TN002 (2) —
Controller, 575 V 2 Hp — — HR46TN003 (2)
Enclosure 30RA500381 (2)
Enclosure Cover 30RA500519 (2)
Enclosure Mounting Bracket 50EJ500656 (2)
Fan Relay HN61KK055 (2)
Relay Base HN79KK035 (2)
Fuse Block HY11UT035 (2)
Fuse 15A, KTK-R, Class CC — HY10KB151 (6) HY10KB151 (6)
Fuse 20A, KTK-R, Class CC HY10KB200 (6) — —
Harness Assembly 48ZZ401971 (2)
Harness Assembly 48EJ402454 (2)
Harness Assembly 48ZZ402001 (2)
Label 48ZZ502002
Transducer HK05ZZ001 (2)
Transducer Harness 48EJ403240 (2)
Varnish Cloth (Large) 48DA510141 (2)
Varnish Cloth (Small) 38C24601 (2)
Wire Tie HY76TB123 (6)
Wire Tie HY76TB045 (2)
Wire, 16 Gage 72 in. Long WHT (2), GRY (2)
UNIT VOLTAGE ITEM DESCRIPTION
48/50P030-060
208/230 CRLOWAMB033A00
380, 400, 460 CRLOWAMB034A00
575 CRLOWAMB035A00
48/50P070-100
208/230 CRLOWAMB036A00
380, 400, 460 CRLOWAMB037A00
575 CRLOWAMB038A00
WARNING
To avoid the possibility of electrical shock, open all discon-
nects before installing or servicing this accessory.
CAUTION
To avoid damage to refrigerant coils, electrical compo-
nents, and wiring use extreme care when drilling screw
holes and screwing in fasteners.