Carrier 48/50P2 Air Conditioner User Manual


 
14
Table 5 — Program Parameters for the Operating Mode
LEGEND
PARAMETERS DESCRIPTION MODE 1 MODE 2 MODE 4
P01 Line Voltage: 01 = low line, 02 = high line 01 02 02
P02 Carrier Freq: 01 = 4 kHz, 02 = 6 kHz, 03 = 8 kHz 01 01 01
P03 Startup mode: flying restart 06 06 06
P04 Stop mode: coast to stop 01 01 01
P05
Standard Speed source: 01 = keypad, 04 = 4-20mA (NO PI), 05 = R22 or R410A,
06 = R134a
05 05 05
P06 TB-14 output: 01 = none 01 01 01
P08 TB-30 output: 01 = none 01 01 01
P09 TB-31 Output: 01 = none 01 01 01
P10 TB-13A function sel: 01 = none 01 01 01
P11 TB-13B function sel: 01 = none 01 01 01
P12 TB-13C function sel: 01 = none 01 01 01
P13 TB-15 output: 01 = none 01 01 01
P14 Control: 01 = Terminal strip 01 01 01
P15 Serial link: 02 = enabled 9600,8,N,2 with timer 02 02 02
P16 Units editing: 02 = whole units 02 02 02
P17 Rotation: 01 = forward only, 03 = reverse only 01 01 01
P19 Acceleration time: 20 sec 20 20 20
P20 Deceleration time: 10 sec 10 10 10
P21 DC brake time: 0 000
P22 DC BRAKE VOLTAGE 0% 0 0 0
P23 Min freq = 8 Hz ~ 100 – 160 rpm 8 8 8
P24 Max freq 60 60 50
P25 Current limit: (%) 125 110 110
P26 Motor overload: 100 100 100 100
P27 Base freq: 60 or 50 Hz 60 60 50
P28 Fixed boost: 0.5% at low frequencies 0.5 0.5 0.5
P29 Accel boost: 0% 000
P30 Slip compensation: 0% 0 0 0
P31 Preset spd #1: speed if loss of control signal 57 57 47
P32 Preset spd #2: 0 000
P33 Preset spd #3: 0 000
P34 Preset spd 4 default — R22 setpoint. TB12-2 open 24.0 24.0 24.0
P35 Preset spd 5 default — R134a setpoint. TB12-2 closed 12.6 12.6 12.6
P36 Preset spd 6 default 0 0 0
P37 Preset spd 7 default 0 0 0
P38 Skip bandwidth 000
P39 Speed scaling 000
P40 Frequency scaling 50 or 60 Hz 60 60 50
P41 Load scaling: default (not used so NA) 200 200 200
P42 Accel/decel #2: default (not used so NA) 60 60 60
P43 Serial address 111
P44 Password:111 111 111 111
P45
Speed at min signal: 8 Hz; used when PID mode is disabled and 4-20 mA input is
at 4 mA
888
P46
Speed at max feedback: 60 or 50 Hz. Used when PID disabled and 4-20 mA input is
at 20 mA
60 60 50
P47 Clear history? 01 = maintain. (set to 02 to clear) 01 01 01
P48 Program selection: Program 1 – 12 01 02 04
P61 PI Mode: 05 = reverse, 0-5V, 01 = no PID 05 05 05
P62 Min feedback = 0 (0V *10) 0 0 0
P63 Max feedback = 50 (5V * 10) 50 50 50
P64 Proportional gain = 3.5% 3.5 3.5 3.5
P65 Integral gain = .2 .2 .2 .2
P66 PI accel/decel (setpoint change filter) = 10 10 10 10
P67 Min alarm 000
P68 Max alarm 000
NA Not Applicable
PI Proportional Integral
PID Proportional Integral Derivative