Carrier 33PILOT-01 Air Conditioner User Manual


 
7
Pressing the EXIT button causes the System Pilot to return to the
Master Zone Controller (Linkage Coordinator) Default screen.
Holiday (HOLDYxxS) Configuration Table —
The Holiday Configuration Table is shown in Table 1. The Sys-
tem Pilot has 30 configurable Holiday tables (HOLDY01S –
HOLDY30S). An explanation of each configuration decision
follows.
START MONTH — Use this decision to indicate the month
of the year in which the holiday will begin.
Start Month: Allowable Entries 1 to 12
Default Value 1
START DAY — Use this decision to indicate the day of the
month on which the holiday will begin.
Start Day: Allowable Entries 1 to 31
Default Value 1
DURATION — Use this decision to indicate the number of
consecutive days that the holiday will last. If you enter 0 in this
decision, the holiday schedule will be disabled.
Duration: Allowable Entries 0 = Disable or 1 to 365
Default Value 0
Table 1 — Holiday Configuration (HOLDYXXS)
DESCRIPTION DISPLAY POINT RANGE DEFAULT
Start Month XX MONTH 1-12 1
Start Day XX DAY 1-31 1
Duration XXX DURATION 0-365 0
Fig. 13 — 3V™ Bus Scan Screen