Carrier 30GX080-265 Air Conditioner User Manual


 
Date: Supersedes: 30GX080-265
AIR-COOLED LIQUID CHILLER
30GX
Rev.:
-4SB
JOB NAME: LOCATION:
BUYER: BUYER P.O. # CARRIER #
UNIT NUMBER: MODEL NUMBER:
PERFORMANCE DATA CERTIFIED BY: DATE:
DESCRIPTION
Packaged air-cooled liquid chiller factory wired, piped, and charged with HFC-134a. Upward
discharge airflow minimizes directional sound and dissipates heat away from surrounding areas.
FEATURES
Cooler is mechanically cleanable ‘‘flooded’’ shell-and-tube type
with removable heads. It is tested and stamped in accordance
with ASME Code for a refrigerant working side pressure of
220 psig (1517 kPa) and a maximum fluid side pressure of
300 psig (2068 kPa) (250 psig [1724 kPa] in Canada) and is
insulated with
3
4
-in. (19 mm) closed-cell polyvinyl chloride foam.
Cooler can be equipped with electric heater to help protect against
cooler freeze-up (use of inhibited glycol anti-freeze recommended
for freeze protection).
Compressor is semi-hermetic twin screw design with refrigerant
gas cooled motor and integral oil filter and discharge gas muffler.
Complete thermal and electrical protection is provided.
Air-cooled condenser is constructed of fins mechanically bonded
to seamless copper tubes. Coils are leak and pressure tested at
450 psig (3103 kPa).
Condenser fans are direct driven 11-blade, shrouded axial type,
statically and dynamically balanced, discharging air vertically
upward, protected by coated steel wire safety guards.
Condenser fan motors are totally enclosed 3-phase with perma-
nently lubricated bearings and Class F insulation (except speed
control motors).
Each refrigerant circuit includes oil separator, high side pressure
relief device, liquid and discharge line shutoff valve, filter drier,
moisture indicating sight glass, expansion/level control device.
Microprocessor control includes keypad with diagnostic display
displaying set points, time, system status (including temperatures,
pressures and % loading) and the alarm conditions.
Automatic compressor lead/lag.
Capacity control based on leaving chilled water temperature with
return water temperature sensing.
7-Day time scheduling of pump(s) and chiller.
60-Hz Models: 080, 090, 106, 115, 125, 136, 151, 161, 176, 206,
226, 251, and 265.
50-Hz Models: 080, 090, 105, 106, 115, 125, 136, 150, 160, 161,
175, 205, 225, 226, 250, and 265.
PERFORMANCE DATA
UNIT
Capacity
Compressor Input Power kW
Unit Input Power
kW
Minimum Outdoor Operating Temperature
Capacity Control Steps
Minimum Capacity % %
EER
Entering Air Temperature
Weight
COOLER
Cooler Fluid
Entering Fluid Temperature
Leaving Fluid Temperature
Flow Rate
Pressure Drop
Fouling Factor
ELECTRICAL DATA
Power Supply to Unit Volts Ph Hz
Power Supply to Control Circuit
Volts Ph Hz
Minimum Amps Circuit 1
Amps
Maximum Fuse Amps Circuit 1
Amps
Control Circuit Fuse Amps
Amps
Maximum Instantaneous Current Flow
Amps
Minimum Amps Circuit 2
Amps
Maximum Fuse Amps Circuit 2
Amps
OPTIONS
2