Carrier 30GX080-265 Air Conditioner User Manual


 
CERTIFIED DIMENSION PRINT
UNIT
30GX
TOTAL OPERATING
WEIGHT
TOTAL OPERATING
WEIGHT
Aluminum Fin Copper Fin
lb kg lb kg
205 12,184 5,538 13,569 6,168
225 12,364 5,620 13,749 6,250
NOTES:
1. Unit must have clearances for air flow as follows:
Top — Do not restrict in any way
Ends — (1524 mm) 5 ft (from solid surface)
Sides — (1829 mm) 6 ft
2. Unit with sound hoods requires clearances for air flow as
follows:
Top — Do not restrict in any way
Ends — (1829 mm) 6 ft
Sides — (2134 mm) 7 ft
3. Center of gravity shown is for aluminum fin coil. See instal-
lation instructions for all other values.
8